Limit And Protective Functions; Maximum Limitation Of The Room Temperature - Siemens Synco 700 Basic Documentation

Modular heating controller rmh760b including extension modules rmz782b, rmz783b, rmz787 and rmz789
Hide thumbs Also See for Synco 700:
Table of Contents

Advertisement

Settings
Deactivation
Activation
134/238
Building Technologies
HVAC Products
Boost heating is activated when a change is made from room operating mode Economy
or Protection
to Comfort
0.25 K or more below the setpoint.
TR
TRSetpt
SetptCmf
SetptEco
TR
Room temperature
TRSetpt
Room temperature setpoint
SetptCmf
Setpoint, room operating mode Comfort or Precomfort
SetptEco
Setpoint, room operating mode Economy or Protection
Δ
SetptTR
Setpoint increase
Main menu > Commissioning > Settings > ... or
Main menu > Settings > Heating circuit 1 (or 2 or 3 ) > Optimizations/influences
Operating line
[Boost heating] setp increase
9.8

Limit and protective functions

9.8.1

Maximum limitation of the room temperature

If a room temperature sensor is connected, maximum limitation of the room tempera-
ture can be activated.
In contrast to room temperature influence with modulating action on the flow tempera-
ture setpoint, maximum limitation of the room temperature works with 2-position control.
When the actual room temperature exceeds the room temperature setpoint by the
adjustable room limitation increase, the heating circuit pump will be deactivated.
When the pump is deactivated, the heating circuit does not call for heat.
When the actual room temperature drops below the switch-off point by the room tem-
perature's switching differential, the heating circuit pump will be activated.
Modular Heating Controller RMH760B
9 Heating circuit control
or Precomfort and when the room temperature lies
SetptTR
TR
Range
0...20 K
Factory setting
5 K
CE1P3133en
05.02.2007