Compressor Control In Plants With Buffer Or Combi Storage Tank - Siemens Albatros2 User Manual

Heat pump controller
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

Switching diff return temp

Compressor control in plants with buffer or combi storage tank

Control
106/221
Siemens Switzerland Ltd
HVAC Products
Required sensors:
To enable the controller to put the heat pump into operation without control of a buffer
or combi storage tank, at least the return temperature sensor (B71) and the relevant
source temperature sensor must be installed. In the case of air-to-water heat pumps,
the evaporator sensor (B84) is required also.
Line no.
Operating line
2840
Switching diff return temp
If the return temperature exceeds the setpoint by half the switching differential, the heat
pump will be switched off; if it falls below the setpoint by half the switching differential,
the controller will put the heat pump into operation.
If the return temperature setpoint drops below 30 °C, the switching differential is
reduced in a way that the switch-on point approaches the setpoint. With a return
temperature setpoint of 20 °C, the switch-on point is identical with the return
temperature setpoint.
T
2840
30°C
20°C
The calculation of the return temperature setpoint is explained on operating line 5810
("Differential HC at OT –10 °C").
The function is not active when heat compensation is switched on.
The settings apply to compressor 1 and – if present – to compressor 2 also.
If a buffer or storage tank is connected to the same controller as the heat pump, the
controller uses sensors B4 and B41 for control of the compressor. The switching
differential (2840) has no impact.
If there is no sensor B41, heat pump return temperature sensor B71 is used.
The setting on operating line 2841 defines whether the minimum compressor running
time (2842) is observed.
As soon as the temperature at both sensors (B4 + B41) drops 1 Kelvin below the flow
temperature setpoint, a heat request is forwarded to the heat pump. This heat request
is maintained until the temperature at both sensors reaches the flow temperature
setpoint.
User manual RVS61.843
6 The settings in detail
OFF
OFF
Switch-off point
ON
Switch-on point
TRLw
2840
Switching diff return temp
ON
Ta
Outside temperature
T
Temperature of heat pump return
TRLw
Return temperature setpoint
Ta
CE1U2355en_02
23. November 2007