Siemens Albatros2 User Manual page 174

Heat pump controller
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

Max starts compr2/hrs run
Curr starts comp2/hrs run
Reset
Diff condens max/week
Cur diff condens
max/week
Reset
Diff condens min/week
Cur diff condens
min/week
Reset
Diff evap max/week
Cur diff evap max/week
Reset
174/221
Siemens Switzerland Ltd
HVAC Products
Maximum number of starts of compressor 2 per hour run
Setting the maximum permissible number of starts of compressor 2 per hour run.
Average number of starts of compressor 2 per hour run, reached over the last 6 weeks.
If the value is above setting "Max starts compr2/hrs run" (7074), symbol
the display and a maintenance message on the info level:
9: Too many starts compr 2 (priority 9)
This parameter can be reset, provided the respective access right is granted.
Number of times per week the temperature differential across the condenser
exceeds the maximum
Setting the number of times within a 7-day period the maximum temperature differential
across the condenser may be exceeded.
Number of times the maximum temperature differential across the condenser was
exceeded within a 7-day period. If the value is above setting "Diff condens max/week"
(7076), symbol
appears on the display and a maintenance message on the info
level:
13: Diff condens max (priority 3)
This parameter can be reset, provided the respective access right is granted.
Number of times per week the temperature differential across the condenser falls
below the minimum
Indicates how many times within a 7-day period the temperature differential across the
condenser may drop below the minimum.
Number of times the temperature differential across the condenser dropped below the
minimum level within a 7-day period. If the value is above setting "Diff condens
min/week" (7078), symbol
the info level:
14: Diff condens min (priority 3)
This parameter can be reset, provided the respective access right is granted.
Number of times per week the temperature differential across the evaporator
exceeds the maximum
Indicates how many times within a 7-day period, the maximum temperature differential
across the evaporator may be exceeded.
Number of times the maximum temperature differential across the evaporator was
exceeded within a 7-day period. If the value is above setting "Diff evap max/week"
(7080), symbol
appears on the display and a maintenance message on the info
level:
15: Diff evap max (priority 3)
This parameter can be reset, provided the respective access right is granted.
User manual RVS61.843
6 The settings in detail
appears on the display and a maintenance message on
appears on
CE1U2355en_02
23. November 2007

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents