Input H1, H3

Function input Hx
Siemens Switzerland Ltd
HVAC Products
These operating lines are used to determine the function of input H1/H3 (Hx).
The selected function is activated by closing a potentialfree contact or by feeding an
analog DC 0...10 V signal to terminal Hx.
Line no.
Operating line
5950
Function input H1, H3
Optg mode changeover HCs+DHW
5960
Optg mode changeover HCs
Optg mode changeover HC1
Optg mode changeover HC2
Optg mode changeover HCP
Error/alarm message
Minimum flow temp setpoint
Heat request 10V
Dew point monitor
Flow temp setp incr hygro
Refrigeration request
Refrigeration request 10V
Pressure measurement 10V
Rel room humidity 10V
Room temp 10V
Release swimming pool
Switch-on command HP stage 1
Switch-on command HP stage 2
5951
Contact type H1, H3
NC
5961
NO
5952,
Function value, contact H1, H3
5962
5953,
Voltage value 1 H1, H3
5963
5954,
Function value 1 H1, H3
5964
5955,
Voltage value 2 H1, H3
5965
5956,
Function value 2 H1, H3
5966
The settings for input H2 are made on operating lines 6046 – 6052.
Changeover of operating mode
• Heating circuits
The operating mode of the respective heating circuit(s) is switched to Protection via
terminal Hx (e.g. by means of a remote telephone switch).
• DHW
DHW heating is locked only when using setting 1 (HCs+DHW) All temperature
requests made by the heating circuits and by DHW are ignored. Frost protection is
maintained.
Error / alarm message
When input H1 closes, a controller-internal error message is triggered.
If the alarm output (relay outputs QX1 – QX6, 5890 – 5896) is appropriately configured,
the error is forwarded or indicated by closing an additional contact (by an external lamp
or horn).