Plant hydraulics
Summary
Primary controller / system pump
Prim contr/system
pump
Siemens Switzerland Ltd
HVAC Products
If none of the Hx inputs is used to release the swimming pool, the swimming pool
priority is determined by the parameter setting. The swimming pool is always enabled
for solar heating.
If the swimming pool is enabled via one of the Hx inputs, swimming pool priority is
equivalent to the parameter setting. Solar heating must now be enabled via the Hx
input.
If 2 Hx inputs are used to enable the swimming pool, the swimming pool is given priority
when both Hx inputs are enabled. If only one of the Hx inputs is enabled, the swimming
pool priority is determined by the parameter setting. If none of the Hx inputs is enabled,
solar heating of the swimming pool is disabled.
Line no.
Operating line
2080
With solar integration
This setting is made to indicate whether the swimming pool can be charged by solar
energy.
6.11 Primary controller / system pump
Y19
Q14
B15
Line no.
Operating line
2150
Prim contr/system pump
Before buffer
After buffer
If the plant uses a buffer storage tank, it is to be set here whether – hydraulically
speaking – the primary controller or the system pump is installed upstream of or
downstream from the buffer storage tank.
User manual RVS61.843
6 The settings in detail
The primary controller makes it possible to mix the flow,
aimed at obtaining flow temperatures for heating / cooling
groups with setpoints higher or lower than those of the
common flow.
The system pump can be used to overcome the pressure
drop to remote heating / cooling groups.
101/221
CE1U2355en_02
23. November 2007