Enclosure
Grounding method
Operating
environment
Battery
Applicable standards
A-2
Item
Ambient operating tempera-
ture
Ambient operating humidity
Atmosphere
Ambient storage tempera-
ture
Altitude
Pollution degree
Noise immunity
Overvoltage category
EMC immunity level
Vibration resistance
Shock resistance
Life
Model
Specification
Mounted in a panel
Ground to less than 100 Ω.
0 to 55°C
10% to 95% (with no condensation)
Must be free from corrosive gases.
-25 to 70°C (excluding battery)
2,000 m max.
2 or less: Meets IEC 61010-2-201.
2 kV on power supply line (Conforms to IEC 61000-4-4.)
Category II: Meets IEC 61010-2-201.
Zone B
Conforms to IEC 60068-2-6.
5 to 8.4 Hz with 3.5-mm amplitude, 8.4 to 150 Hz, accelera-
2
tion of 9.8 m/s
100 min each in X, Y, and Z directions (10 sweeps of 10 min
each = 100 min total)
Gravity acceleration is assumed to be G=9.8 m/s
Conforms to IEC 60068-2-27.
2
147 m/s
, 3 times in X, Y, and Z directions
Gravity acceleration is assumed to be G=9.8 m/s
5 years at 25°C (Power ON time rate 0% (power OFF))
CJ1W-BAT01 (sold separately)
Refer to the OMRON website (http://www.ia.omron.com/) or
consult your OMRON representative for the applicable stand-
ards.
NX-series NX502 CPU Unit Hardware User's Manual (W629)
2
.
2
.

Advertisement

Table of Contents
loading

This manual is also suitable for:

Nx502-1 00 series

Table of Contents