In most situations (Especially if brand new racked system and IBM Cumulus switch), you will
press Enter immediately to use VLAN tag 101.
Figure 68. Configuring VLAN tag
r. Highlight the Confirm BMC VLAN tag menu and press Enter. This confirms the VLAN tag set in the
previous option.
Figure 69. Confirming VLAN tag
s. Highlight the Run passwordless ssh check menu and press Enter. This option checks that
passowordless ssh is set up correctly.
The result must be "passwordless test is PASSED".
If the test Fails, run the next option to fix.
t. Highlight the Fix passwordless ssh menu and press Enter. This fixes passwordless ssh issues
that are found in the prior step.
u. Check the memory (ESS 3200).
The result is,
InspectionPassed: True
If you do not see this result, debug faulty DIMMs.
v. Check the CPU (ESS 3200).
The result is,
InspectionPassed: True
If you do not see this result, debug faulty CPUs.
w. Do not run the Check for any incorrectly formatted drives option. This option will be modified in
the future.
3. Fix VLAN IP address issue on the BMC.
Figure 70. SSR Checks for p9 EMS
Note: This applies to p9 EMS or p9 protocol node.
74  IBM Elastic Storage System 3200: Hardware Planning and Installation Guide