Installation
All vent pipe joints must be sealed to prevent leakage. Follow
the instructions provided with the approved venting materials.
Vent pipe shall be sized as follows:
Input ratings
Btu/h
W
75000–149999
21980–43958
150000–400000
43960–117228
The total equivalent length of vent pipe must not exceed 50 ft
(15.25 m). Equivalent length is the total length of straight
sections, plus 5 ft (1.52 m) for each 90° elbow and 2.5 ft
(0.76 m) for each 45° elbow.
The vent system must also be installed to prevent collection of
condensate. Pitch horizontal pipe runs downward 1/4 in./ft
(21 mm/m) toward the outlet to permit condensate drainage.
Insulate vent pipe exposed to cold air or routed through
unheated areas. Insulate vent pipe runs longer than 10 ft
(3 m). Insulation should be a minimum of 1/2 in. (12 mm) thick
foil faced fiberglass of 1-1/2# density. Maintain 6 in. (152 mm)
clearance between vent pipe and combustible materials.
An approved Breidert Type L, Field Starkap or equivalent vent
cap must be provided. Vent cap inlet diameter must be the
same as the vent pipe diameter. The vent terminal must be at
least 12 in. (305 mm) from the exterior wall that it passes
through to prevent degradation of building material by flue
gases. The vent terminal must be located at least 12 in.
(305 mm) above grade, or in snow areas, at least 3 ft (1 m)
above snow line to prevent blockage. Additionally, the vent
terminal must be installed with a minimum horizontal clearance
of 4 ft (1.2 m) from electric meters, gas meters, regulators or
relief equipment.
Through-the-wall vents shall not terminate over public
walkways or over an area where condensate or vapor could
create a nuisance or hazard. Provide vent termination
clearances to building or structure features as follows:
Structure
Door, window or gravity inlet
Forced air inlet within 10 ft (3 m)
Adjoining building or parapet
Adjacent public walkways
Figure 139. Horizontal venting—category III
1 ft (305 mm) Min.
Approved
2 in. (51 mm) Fiberglass Insulation
Vent Terminal
3 ft (0.91 m) Min.
Above Highest Snowfall
84
Diameter pipe to use
in.
mm
5
126
6
152
Minimum Clearance
4 ft (1.2 m) below
4 ft (1.2 m) horizontally
1 ft (305 mm) above
3 ft (0.91 m) above
6 ft (1.8 m)
7 ft (2.1 m) above grade
5 ft (1.52 m) Min.
50 ft (15.25 m) Max.
Equivalent Length
2 in (51 mm) Clearance
Thimble with
Condensate Drain
With Trap, If Required
By Local Codes
Heating Appliance

Hot Water Connection Size and Location

Figure 140. OAD water inlet and outlet, in. (cm)
Water
inlet
31.055 (78.9)
Figure 141. OAN water inlet and outlet, in. (cm)
INSTALLING CONTRACTOR TO CUT HOLES
IN CABINET SIDE PANEL FOR WATER PIPE
PENETRATION (3" NOMINAL MNPT)
WATER INLET
3.347
12.902
9.556
45.096
27.500
72.596
Installing contractor to
cut holes in cabinet side wall
for water pipe penetration
(2 in. [5.1 cm] nominal MNPT).
2.865 (7.3)
18.807
Water
15.943
(47.8)
(40.5)
outlet
0.890 (2.3)
63.000 (160.0)
WATER OUTLET
OAU-SVX007A-EN