DC Conductors
Table 13. Zone sensor module wiring
Distance from Unit to Control
000–150 feet
0–45.7 m
151–240 feet
46–73.1 m
241–385 feet
73.5–117.3 m
386–610 feet
117.7–185.9 m
611–970 feet
186.2–295.7 m
Figure 142. OAUTS connection B
FOR THUMBWHEEL DO NOT USE
TEMPERATURE SENSOR BAYSENS036,
INSTEAD USE BAYSENS074.
BAYSENS074A
VELSEN-0049
(THUMBWHEEL)
REMOVE JUMPER AND INSTALL FIELD
SUPPLIED DRY CONTACT OR SWITCH.
CLOSURE BETWEEN OAUTS-7 AND OAUTS-8
ENABLES "OCCUPIED MODE".
FIELD INSTALLED
WATER VALVES
DISCHARGE AIR TEMPERATURE SENSOR
TEMP. ONLY:
VELSEN-0021
TE-DFG-B1244-00
Factory-Provided Sensors
A discharge temperature sensor (VELSEN-0021) will be
factory-provided for field installation in the supply duct. Refer
to
Figure 149, p. 108
for installation instructions.
If space control is selected, a combination space temperature/
humidity sensor (BAYSENS036A) will be factory-provided for
field installation in the space. Refer to
installation instructions.
If multi-zone VAV control is selected, a static pressure sensor
(VELCON-0976) will be factory-provided for field installation in
the supply duct or space. Refer to
installation instructions.
OAU-SVX007A-EN
Recommended Wire Size
22 gauge
2
0.33 mm
20 gauge
2
0.50 mm
18 gauge
2
0.75 mm
16 gauge
2
1.3 mm
14 gauge
2
2.0 mm
FACTORY
SUPPLIED
JUMPER
BAYSENS036A
VELSEN-0024
(TEMP/HUM
COMBO SENSOR)
OAUTS
SPTC
SPTC
t°
1
VTSP
3
5
7
9
11
13
15
17
19
21
23
TEMP./HUM.:
VELCON-0608
RHP-3D1B
DTC
t°
Figure 150, p. 109
Figure 152, p. 111
for
VELCON-0976
BA/ZPM-SR-ST-D
SDPC
OUT
GND
V+
2
VELSEN-0024
4
BAYSENS036A
6
SPHC
H
8
TO SHUT DOWN THE UNIT FOR EMERGENCY STOP,
10
REMOVE JUMPER FROM OAUTS-9 AND OAUTS-10 AND
INSTALL FIELD SUPPLIED DEVICE.
12
14
16
18
SR DPC
20
V+
22
OUT
24
GND
VELCON-0976
BA/ZPM-SR-ST-D
If modulating OA/RA dampers w/economizer and an exhaust
fan are selected, a duct static pressure sensor
(VELCON-0350) will be factory-provided for field installation in
the return duct. Refer to
instructions.
for
Installation
Figure 152, p. 111
for installation
89