Trane Horizon OABD Series Installation, Operation And Maintenance Manual page 104

Outdoor air unit
Table of Contents

Advertisement

Alarms and Troubleshooting
Table 19.
Mitsubishi VFD programming parameters
575V
Parameter
Setting
1
Max Hz
2
Min Hz
7
30 s
8
30 s
9
Motor FLA
38
Max Hz
39
Max Hz
67
5
71
3
73
1
152
6 %
153
1 s
190
0
79
2
77
1
Digital Scroll Compressor Controller
Units with digital scroll compressor controller provides control,
protection, and diagnostics for the digital compressor system.
It also modulates or cycles the unloader solenoid in an ON/
OFF pattern based on capacity demand signal from the system
controller.
Figure 147. Digital scroll compressor controller
POWER LED (Green) - Voltage is present at the 24VAC power
terminals. When the anti-short cycle timer is active, the green
LED will flash.
UNLOADER LED (Yellow) - Unloader solenoid status. This
LED is ON when the unloader solenoid is energized.
ALERT LED (Red) - Communicates an abnormal system
condition through a unique flash code. The ALERT LED will
flash a number of times consecutively, pause and then repeat
the process. The number of consecutive flashes, defined as
the flash code
(Table
20), correlates to a particular abnormal
condition.
While each ALERT code is active, the alarm relay contacts (A1
and A2) are closed. The ALERT code will remain active, and
104
Description
Maximum Frequency
Minimum Frequency
Acceleration Time
Deceleration Time
Electronic Thermal O/L Relay
Maximum Frequency
Maximum Frequency
Number of Retries at Fault Occurrence
Applied Motor
Analog Input Selection
Zero Current Detection Level
Zero Current Detection Time
RUN Terminal Function Selection
Operative Mode Selection
Parameter Write Selection
the alarm relay contacts closed until the reset conditions have
been met or 24VAC power has been cycled OFF and ON. All
flash codes except code 6 and 8 result in the compressor
contactor, unloader solenoid and vapor injection solenoid
being deenergized. Flash codes 3, 4, 5, and 9 activate the 2-
minute anti-cycle timer. Flash code 2 activates the 30-minute
timer. All LEDs flashing at the same rate indicates 24VAC
supply is too low for operation.
All LEDs on solid at the same time indicate digital scroll
compressor controller failure.
Whenever power is cycled OFF and ON, the current flash code
and all internal counters are reset.
Table 20. Digital scroll compressor controller flash code
details
Trouble
Possible Cause
Compressor limit switch(es) open.
Compressor limit switch(es) open.
Digital Scroll Compressor
not running.
Minimum on/off time.
Refer to digital scroll controller alarm flash code.
Digital Scroll Compressor Controller Alert Flash Codes
Code 1
Reserved for future use.
Code 2
High Discharge Temperature.
Code 3
No current when compressor should be running.
Code 4
Locked Rotor.
Code 5
Normal operation when compressor is disabled.
Code 6
Thermistor Fault. Thermistor is not connected.
Code 7
Revere for future use
Current is detected when compressor should be
Code 8
OFF.
Supply voltage to controller dropped below 18.5
Code 9
VAC.
Variable Speed Compressor Drive
Units with variable speed compressor drive deliver maximum
machine performance with sensor less permanent magnet
motor control, for dynamic and efficient machine operation.
Figure 148. Variable speed compressor HOA-keypad
OAU-SVX007A-EN

Hide quick links: