Figure 151. Supply duct static pressure transducer (SDPC)
INSTALLATION INSTRUCTIONS FOR (BAPI) OR (BELIMO)
SUPPLY DUCT STATIC PRESSURE TRANSDUCER (SDPC)
GENERAL:
SDPC IS USED TO CONTROL SUPPLY FAN SPEED BASED ON STATIC PRESSURE. DEFAULT FOR SDPC IS 0-2" WC TO
0-10VDC. ANY OTHER SETTING MUST BE RE-CONFIGURED WITHIN THE MAIN UNIT CONTROLLER.
IF A DUCT STATIC PRESSURE GREATER THAN 1.5"WC IS DESIRED, IT'S RECOMMENDED TO INCREASE THE RANGE OF THE
TRANSDUCER AND RE-CONFIGURE THE MAIN UNIT CONTROLLER.
INSTALLATION:
1.
VERIFY DIP SWITCH AND DIAL SETTINGS ACCORDING TO CHART BELOW.
2.
MOUNT TRANSDUCER ON THE EXTERIOR OF THE DUCT AT LEAST 4 FT FROM THE UNIT.
3.
INSTALL SAMPLING TUBE ONTO THE DUCT AND CONNECT TUBING TO PORT "H" ON TRANSDUCER.
4.
LEAVE PORT "L" ON TRANSDUCER OPEN.
5.
RUN WIRING FROM THE TRANSDUCER TO THE FIELD WIRING TERMINAL (OAUTS) STRIP USING COPPER
CONDUCTORS ONLY.
6.
LAND THE WIRING ON FIELD WIRING TERMINAL STRIP ACCORDING TO THE CHART BELOW.
TRANSDUCER SETTINGS
O3 = 0-10 VOLTS
R2 = 2"WC
#1 OFF = UNIDIRECTIONAL
#2 OFF = INCHES
#3 OFF = SLOW
O4
R4
O5
R5
O3
R3
O2
R2
O1
R1
KCC PART NUMBER: VELCON-0976
SENSOR MODEL NUMBER: BA/ZPM-SR-ST-D
LINES 74 ON UNIT WIRING DIAGRAM
OAUTS-21
SDPC
OAUTS-1
OUT
V+
OAUTS-2
GND
OAUTS FIELD WIRING TERMINAL STRIP
UPDATED 12/13/2021
REV. D
110
TRANSDUCER SETTINGS
#1 ON = 0-2" WC
#2 OFF = 0-2" WC
#3 OFF = 0-2" WC
#4 ON = SLOW
1 2 3
#5 OFF = 0-10 VOLTS
#6 ON = INCH WC
ON
1 2 3
KCC PART NUMBER: VELCON-0067
OFF
SENSOR MODEL NUMBER: 22ADP-584L
LINES 74 ON UNIT WIRING DIAGRAM
OAUTS WIRING
OAUTS-21 -- PWR
OAUTS-1 -- VOUT
OAUTS-2 -- GND
ON
4 5 6
OFF
LOW VOLTAGE FIELD WIRING
TYPICAL DUCT
INSTALLATION
ROOF CURB
RETURN DUCT
SUPPLY DUCT STATIC
PRESSURE TRANSDUCER
SUPPLY DUCT
OAU-SVX007A-EN
NOTE: ROOF
NOT SHOWN