Unit Clearances, Curb Dimensions, and Dimensional Data

OAD Units

Unit Clearances

Figure 82. Installation clearances for units with no
powered exhaust or ERV, in. (cm)
48.000
[121.9]
36.000
[91.4]
52
36.000
[91.4]
44.00
[111.3]
Figure 83. Installation clearances for unit with powered
exhaust but no ERV, in. (cm)
36.00
[91.4]
36.00
[91.4]
Note: 72 in. (182.9 cm) clearance is required above the
condenser fans.
Figure 84. Installation clearances for unit with ERV, in.
(cm)
48.000
[121.9]
36.000
[91.4]
Note: 72 in. (182.9 cm) clearance is required above the
condenser fans.
Figure 85. Unit to unit clearance, in. (cm)
(213.4)
36.00
[91.4]
48.00
[121.9]
36.000
[91.4]
60.000
[152.4]
84
84
(213.4)
OAU-SVX007A-EN