Trane Horizon OABD Series Installation, Operation And Maintenance Manual page 105

Outdoor air unit
Table of Contents

Advertisement

The variable speed compressor drive parameter locations
consist of a two-digit number (menu location) and a three-digit
number (parameter location) that are setup from the factory
based on the unit nameplate and values from
Table 22
for ZPV066 compressors.
Table 21.
Variable speed compressor drive
programming based on cabinet size
Unit
B060, B072, G120, G144, D060, D072
B084
G180, D180
B096
G210
B108
G240
Table 22.
Parameters reference for ZPV066
compressors/-124 VS drive only
Parameter
Description
00.077
User Security Status
07.011
Al2 Control
07.012
Scaling (see table)
07.014
Destination Address
07.015
A13 Control
07.016
Scaling
07.018
Destination Address
00.006
Configuration control parameter
00.032
Soft-start speed
00.033
Soft start acceleration
00.035
Normal running acceleration
00.036
Normal running deceleration
00.037
Shutdown deceleration
00.038
Shutdown hold speed
00.039
Controlled shutdown dwell time
00.040
Stop deceleration
00.041
Oil boost threshold speed
00.042
Oil boost threshold time
00.043
Oil boost acceleration rate
00.044
Oil boost deceleration rate
10.030
N/A
10.031
N/A
10.061
N/A
00.000
Save Parameters
OAU-SVX007A-EN
Table 21
and
Pr 07.012
RPM
-124
3600
0.5
3900
0.542
4400
0.611
4500
0.625
4700
0.653
4900
0.681
5400
0.75
Value
All menus (1)
Volt
-
29.017
Thermo-No Trip
1
29.045
00 0010
0000 1000
1800 rpm
3s
10s
10s
10s
1000 rpm
15s
10s
1800 rpm
120 min
10s
10s
0
0
0
On
Alarms and Troubleshooting
105