Chapter 3
Hardware Installation and Initial Configuration

Rack Mounting

1
18
Application Gateway Hardware Installation Guide
WARNING
MAIN AC POWER DISCONNECT
You must install an AC power disconnect for the
entire rack unit. This main disconnect must be
readily accessible, and it must be labeled as
controlling power to the entire unit, not just to
the Application Gateway(s).
Damage to Equipment
OVERCURRENT PROTECTION
The Application Gateway is designed for an AC
line voltage source with up to 20 amperes (A) of
over-current protection. If the power system for
the equipment rack is installed on a branch
circuit with more than 20 A of protection, provide
supplemental protection for the Application
Gateway. If more than one Application Gateway
is installed in the rack, the power source for each
Application Gateway must be from a separate
branch circuit.
To rack mount the Application Gateway:
Attach the rack-mount brackets (B in
the equipment rack. Install the left and right side at an equal height. Use
standard length screws from the accessories pouch, and screw them into
the top and bottom drill holes of the bracket. See
Figure 4 on page
13) to the front of
Figure 9 on page
19.