6.3 Scale Conversion (AFP7TC8 Voltage/Current Range Only)

Overview of functions
● This function makes it possible to convert values to an easy-to-use data range. Analog input
data acquired in a range between preset minimum and maximum values is scale converted
and stored in the I/O area. This function is convenient if used for scale unit conversion.
● Scale conversion is executed on a channel-by-channel basis.
● Conversion values read from the analog input unit include fractions. Therefore, convert the
values to easy-to-handle figures if needed.
(K)
+25000
+12500
+1
Configuration
Name
Function
Scale
setting
conversion
Minimum value of scale
conversion
Maximum value of scale
conversion
(Note 1)
If data outside the minimum or maximum scale is input, scale conversion will be disabled and the
minimum or maximum scale value will be stored as a conversion value.
WUME-FP7TCRTD-04

6.3 Scale Conversion (AFP7TC8 Voltage/Current Range Only)

(V)
+3
+5
Default
Not
execute
K0
K10000
(K)
+10000
+5000
Scale
conversion
Setting range and description
Select "Execute".
Set the minimum value at the time of using the scale conversion
function.
Setting range: -3000 to +30000 (specified with a signed integer)
Set the maximum value at the time of using the scale conversion
function.
Setting range: -3000 to +30000 (specified with a signed integer)
+1
+3
+5
(V)
6-7