Advertisement

I/O allocation
The I/O numbers in the timing chart and program are shown on the condition that the starting
word number of the unit is "10". Actual I/O numbers allocated to the analog input unit are
determined by the starting word number.
*1 Disconnection
detection execution
relay
*2 Disconnection
detection flag
Configuration
Name
Disconnection
detection
Function
setting
Disconnection
detection reset
Sample program
R0
DF
( (
) )
R1
DF
( (
) )
X110
Disconnection
detection flag
● Not executed unless thermocouple, a voltage input range of +1 to +5 V or current input range
of +4 to +20 mA is set. This function will not be executed even if the disconnection detection
execution relay is turned ON when the disconnection detection has been set to "Not execute" in
the configuration.
WUME-FP7TCRTD-04
CH0
CH1
CH2
Y100
Y110
Y120
X110
X130
X150
Default
Setting range and description
Not
Select "Execute".
execute
Auto
Select "Auto".
6.6 Disconnection Detection (AFP7TC8)
CH3
CH4
Y130
Y140
X170
X190
Y100
<
SET
>
Disconnection
detection
execution relay
Y100
<
RST
>
Y200
CH5
CH6
CH7
Y150
Y160
Y170
X210
X230
X250
(CH0): Controls
disconnection detection
execution function
ON : Execute
OFF: Turns OFF
disconnection detection
flag
(CH0): Turns Y200 ON at
the time of disconnection
detection
6-15