6.1 Average Processing Settings
● If "moving average" is set, analog input data items acquired will be stored in unit memory
(UM) as digital values when the number of analog input data items reaches the set number
of moving average times.
● When the set number of moving average times is 3 to 64, the maximum and minimum values
are cut from the data for n times, and the data for (n-2) times is averaged.
● When the set number of moving average times is 1 or 2, the latest measured data is stored
without averaging processing.
● When data sampling for the set number of times has not been completed, data is not
updated. When all data are acquired, the data will be updated.
● Obtain output (moving average value) to be processed from the following input.
The number of average times, analog input data for the number of average times, the latet analog
Input
input data, and old analog input data
Output
Moving average value
Processing during moving average
Averaging setting example: "moving average", number of averaging times set to 15.
a
Analog signal
Analog input
processing
Analog input
data
Configuration
Name
Average processing
Function
setting
Averaging constant
6-4
e
f
g
d
c
b
Average of a to o (Max. and min. values are cut.)
Average of b to p (Max. and min. values are cut.)
Average of c to q (Max. and min. values are cut.)
Default
Not execute
U8
h
i
m
j
k
l
Setting range and description
Select "moving average".
Number: 3 to 64 [times] (specified with an unsigned
integer)
p
o
q
r
n