Unit configuration
Configuration
N o t e

6.5 Scale conversion

Configuration
32
Name
Default Setting range
Offset/gain
Disable Select "Enable"
processing
Offset value
0
Gain value
10000
The offset adjustment is applied to the unscaled value.
Use scale conversion to set an easy-to-use data range. The digital input
values are scaled to values in the specified range between preset minimum
and maximum values before they are written to the CPU's output area. This
function is convenient if used for unit conversion.
Scale conversion is executed on a channel-by-channel basis.
Name
Default Setting range
Scale conversion
Disable Select "Enable"
Upper limit of
10000
scale
Lower limit of
0
scale
To apply the setting, "Offset/gain processing" must be
enabled.
Setting range: -3000 to +3000 (specified with a signed
integer)
To apply the setting, "Offset/gain processing" must be
enabled.
Setting range: +9000 to +11000 corresponding to a
gain factor of 0.9x–1.1x (specified with a signed inte-
ger)
To apply the setting, "Scale conversion" must be ena-
bled.
Setting range: -30000 to +30000 (specified with a
signed integer)
FP7 Analog Output Unit User's Manual