6.1 Average Processing Settings
6.1 Average Processing Settings
6.1.1 Number of Averaging Times
■
Overview of functions
● Analog input data sampled by the unit is averaged and stored as digital values.
● If the "number of averaging time" is set, analog input data items acquired will be stored in
unit memory (UM) as digital values when the number of analog input data items reaches the
set number of averaging times.
● If the number of data items acquired is less than the number of averaging times, the first
acquired data will be stored in the I/O area.
● Obtain the number of averaging times to be processed from the following input.
Input
The sum of analog input data items for the number of averaging times
Output
Number of averaging times value
■
Processing during the number of averaging times
Averaging setting example: "number of averaging times", number of samples set to
5.
a
Analog signal
Analog input
processing
Analog input
data
■
Configuration
Name
Average processing
Function
setting
Averaging constant
6-2
e
f
g
d
c
b
Average of a to e
Default
Not execute
U8
h
i
m
j
k
l
Average of f to j
Setting range and description
Select "number of averaging times".
Number: 2 to 60000 [times] (specified with an unsigned
integer)
p
o
q
r
n
Average of k to o
WUME-FP7TCRTD-04