5.2 Input Conversion Characteristics (AFP7RTD8)
Conversion characteristics graph
● Up to the lower limit -15 °C and the upper limit +15 °C of the range, reference values which
the conversion accuracy is not assured are indicated.
● When exceeding the upper limit of the range +30°C, converted values are"30000".( For
Pt1000, the upper limit of the range is +20 °C or more.)
Range
Pt100 Range1
JPt100Range1
Pt100 Range2
JPt100 Range2
Pt1000
(Note): The converted value is +30000 when the input is disconnected.
5-8
Input value
-115℃or less
+ 215℃or more
+ 230℃or more
-215℃or less
+ 665℃ or more0℃
+ 680℃ or more
-115℃ or less
+ 115℃~+120℃℃
+ 120℃ or more
Converted value
-1150
+ 2150
+30000
-2150
+ 6650
+30000
-1150
+ 1150
+30000