Troubleshooting
October 2016
Table 5-3. Resource Block SUMMARY_STATUS Messages
Condition name
Uninitilized
No repair needed
Repairable
Call Service Center
Table 5-4. Resource Block DETAILED_STATUS Messages
Condition name
LOI Transducer block error
Sensor Transducer block error
Mfg. Block integrity error
Non-Volatile memory integrity error
ROM integrity error
ADB transducer block error
5.6

Sensor Transducer Block

This section describes error conditions found in the Sensor Transducer Block. Read
Table 5-7
Table 5-5. Sensor Transducer Block BLOCK_ERR Messages
Condition name and description
Other
Out of Service: The actual mode is out of service
Table 5-6. Sensor Transducer Block XD_ERR Messages
Condition name and description
Electronics Failure: An electrical component failed
I/O Failure: An I/O failure occurred
Data Integrity Error: Data stored in the device is no longer valid due to a non-volatile
memory checksum failure, a data verify after write failure, etc.
Algorithm Error: The algorithm used in the transducer block produced an error due to
overflow, data reasonableness failure, etc.
60
to determine the appropriate corrective action.
Recommended action
1. Restart processor.
2. Check display connection.
3. Call service center.
1. Restart processor.
2. Check SuperModule
cable.
3. Call service center.
1. Restart processor.
2. Call service center.
1. Restart processor.
2. Call service center.
1. Restart processor.
2. Call service center.
1. Check impulse lines.
2. Check anomaly detected (SPM).
3. Call service center.
Reference Manual
00809-0200-4801, Rev DA
Table 5-5
through
Troubleshooting