Reference Manual
00809-0100-4802, Rev BA
August 2007
Rosemount 3051S Wireless Series Scalable
Pressure, Flow, and Level Solutions
www.rosemount.com

Advertisement

Table of Contents
loading

Summary of Contents for Emerson Rosemount 3051S

  • Page 1 Reference Manual 00809-0100-4802, Rev BA August 2007 Rosemount 3051S Wireless Series Scalable Pressure, Flow, and Level Solutions www.rosemount.com...
  • Page 3 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Rosemount 3051S Wireless Series Scalable Pressure, Flow, and Level Solutions NOTICE Read this manual before working with the product. For personal and system safety, and for optimum product performance, make sure you thoroughly understand the contents before installing, using, or maintaining this product.
  • Page 4 August 2007 NOTICE The Rosemount 3051S and all other wireless devices should be installed only after the 1420 Wireless Gateway has been installed and is functioning properly. Wireless devices should also be powered up in order of proximity from the 1420 Wireless Gateway, beginning with the closest.
  • Page 5: Table Of Contents

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Table of Contents SECTION 1 Using This Manual ..........1-1 Models Covered .
  • Page 6 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 SECTION 3 Overview............3-1 Safety Messages .
  • Page 7 Rosemount 3051S Series Coplanar ......A-12 Rosemount 3051S Series In-Line ......A-17 Rosemount 3051S Series Liquid Level .
  • Page 8 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007...
  • Page 9: Using This Manual

    USING THIS MANUAL The sections in this manual provide information on installing, operating, and ® maintaining the Rosemount 3051S Wireless pressure transmitter with HART protocol. The sections are organized as follows: • Section 2: Configuration provides instruction on commissioning and operating 3051S Wireless transmitters.
  • Page 10: Models Covered

    Pressure Transmitter Measurement Type Performance Class Differential Gage Absolute Classic Rosemount 3051S Wireless In-Line Pressure Transmitter Measurement Type Performance Class Differential Gage Absolute Classic – Rosemount 3051S Wireless Liquid Level Pressure Transmitter Measurement Type Performance Class Differential Gage Absolute Classic...
  • Page 11: Service Support

    To expedite the return process outside of the United States, contact the nearest Rosemount representative. Within the United States, call the Emerson Process Management Instrument and Valves Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
  • Page 12 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007...
  • Page 13: Overview

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Section 2 Configuration Overview ........page 2-1 Safety Messages .
  • Page 14: Commissioning On The Bench With Hart

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 COMMISSIONING ON Commissioning consists of testing the transmitter and verifying transmitter configuration data. 3051S Wireless transmitters can be commissioned either THE BENCH WITH HART before or after installation. Commissioning the transmitter on the bench before installation using a 375 Field Communicator or AMS ensures that all transmitter components are in working order.
  • Page 15: Review Configuration Data

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 REVIEW NOTE Information and procedures in this section that make use of Field CONFIGURATION DATA Communicator fast key sequences and AMS assume that the transmitter and Fast Keys 1, 5 communication equipment are connected, powered, and operating correctly.
  • Page 16: Field Communicator

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 FIELD COMMUNICATOR Menu Tree 1. PROCESS 1. Pressure VARIABLES 2. Percent of Range 3. Sensor Temperature 4. Supply Voltage 5. Process Variable is 1. Master Reset 1. Logged Sensor Status 2.
  • Page 17: Fast Key Sequence

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Fast Key Sequence The following menu indicates fast key sequences for common functions. A check ( ) indicates the basic configuration parameters. At minimum, these parameters should be verified as part of the configuration and startup procedure.
  • Page 18: Sensor Temperature

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Right click on the device and select “Process Variables...” from the menu.The process variable screen displays the following process variables: • Pressure • Percent of range • Sensor temperature •...
  • Page 19: Security (Write Protect)

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Field Communicator Enter the fast key sequence “Set Output (Transfer function).” Right click on the device and select “Configure/Setup” from the menu. 1. In the Basic Setup tab, use “Xfer fnctn” drop down menu to select output, click Apply.
  • Page 20: Detailed Setup

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 See “LCD Screen Messages” on page 5-6 for more information on LCD messages. LCD Display Configuration Fast Keys 1, 3, 7 Right click on the device and select “Configure/Setup” from the menu.
  • Page 21: Sensor Temperature Unit

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Field Communicator To configure the process alerts with a Field Communicator, perform the following procedure: From the HOME screen, follow the fast key sequence “Alerts.” (1 Device Setup, 3 Configuration, 4 Device Output Configuration, 4 Alerts) Select 1 for HI-HI Alert.
  • Page 22: Advanced Functions For Hart Protocol

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 ADVANCED FUNCTIONS FOR HART PROTOCOL Saving, Recalling, and Use the cloning feature of the Field Communicator or the AMS “User Configuration” feature to configure several 3051S Wireless transmitters Cloning Configuration similarly.
  • Page 23 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 NOTE The transmitter receiving cloned data must have the same software version (or later) as the original transmitter. AMS creating a Reusable Copy To create a reusable copy of a configuration perform the following procedure: 1.
  • Page 24: Device Network Configuration

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 DEVICE NETWORK CONFIGURATION Network In order to communicate with the 1420 Wireless Gateway, and ultimately the Information System, the transmitter must be configured to communicate over Fast Keys 1, 4, 3, 1 the wireless network.
  • Page 25: Overview

    The information in this section covers installation considerations. A Quick Installation Guide (document number 00825-0100-4802) is shipped with every transmitter to describe basic installation and startup procedures. Dimensional drawings for each Rosemount 3051S Wireless variation and mounting configuration are included in Appendix A: Specifications and Reference Data.
  • Page 26: Considerations

    00816-0100-3045 on www.rosemount.com. IMPORTANT The Rosemount 3051S and all other wireless devices should be powered only after the 1420 Wireless Gateway has been installed and is functioning properly. Wireless devices should also be powered up in order of proximity to the 1420 Wireless Gateway, beginning with the closest.
  • Page 27: Environmental

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 NOTE When the transmitter is mounted on its side, position the Coplanar flange to ensure proper venting or draining. Mount the flange as shown in Figure 3-2 on page 3-9, keeping drain/vent connections on the bottom for gas service and on the top for liquid service.
  • Page 28: Installation Procedures

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 INSTALLATION For dimensional drawing information refer to Appendix A: Dimensional Drawings on page A-10. PROCEDURES Process Flange Orientation Mount the process flanges with sufficient clearance for process connections. For safety reasons, place the drain/vent valves so the process fluid is directed away from possible human contact when the vents are used.
  • Page 29 Monel Head Marking Bolt Installation Only use bolts supplied with the Rosemount 3051S or sold by Emerson Process Management as spare parts. When installing the transmitter to one of the optional mounting brackets, torque the bolts to 125 in-lb. (0,9 N-m). Use the following bolt installation procedure: 1.
  • Page 30 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 GAGE/ABSOLUTE TRANSMITTER DIFFERENTIAL TRANSMITTER Drain/Vent Plug Drain/Vent Drain/Vent 1.75 (44) x 4 1.75 (44) x 4 1.50 (38) x 4 1.50 (38) x 4 NOTE Dimensions are in inches (millimeters).
  • Page 31 Flange Bolts 1.75 (44) Adapter Bolts 1.50 (38) Flange/ Adapter Bolts 2.88(73) (1) DIN-compliant traditional flange requires 1.75 in. (44 mm) length adapter bolts. (2) Rosemount 3051S In-line transmitters are direct mount and do not require bolts for process connection.
  • Page 32 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Impulse Piping The piping between the process and the transmitter must accurately transfer the pressure to obtain accurate measurements. There are five possible sources of error: leaks, friction loss (particularly if purging is used), trapped gas in a liquid line, liquid in a gas line, and density variations between the legs.
  • Page 33 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Mounting Requirements Refer to Figure 3-2 for examples of the following mounting configurations: Liquid Flow Measurement • Place taps to the side of the line to prevent sediment deposits on the process isolators.
  • Page 34: Process Connections

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Process Connections 3051S Wireless transmitter flange process connection size is –18 NPT. Flange adapters with –14 NPT connections are available as the D2 option. Use your plant-approved lubricant or sealant when making the process connections.
  • Page 35: Consider Housing Rotation

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 ® Whenever you remove flanges or adapters, visually inspect the Teflon O-rings. Replace them if there are any signs of damage, such as nicks or cuts. If you replace the O-rings, re-torque the flange bolts after installation to compensate for cold flow.
  • Page 36: Battery Installation

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Battery Installation Figure 3-4. Battery Installation Wireless Battery Installation To make connections, perform the following procedure: 1. Remove the housing cover on the battery compartment side. The battery supplies all power to the transmitter. Plug and seal both conduit connections on the transmitter housing to avoid moisture accumulation in the terminal side.
  • Page 37: Rosemount 305 Integral Manifold Installation Procedure

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Figure 3-5. Optional LCD Display LCD Display Meter Cover ROSEMOUNT 304, 305 The Rosemount 305 is available in two designs: Traditional and Coplanar. The traditional 305 Integral Manifold can be mounted to most primary AND 306 INTEGRAL elements with mounting adapters in the market today.
  • Page 38: Rosemount 306 Integral Manifold Installation Procedure

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 2. Install the Integral Manifold on the SuperModule. Use the four 2.25-in. manifold bolts for alignment. Finger tighten the bolts, then tighten the bolts incrementally in a cross pattern to final torque value. See “Flange Bolts”...
  • Page 39: Rosemount 304 Conventional Manifold Installation Procedure

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Rosemount 304 To install a 304 Conventional Manifold to a 3051S Wireless transmitter: Conventional Manifold 1. Align the Conventional Manifold with the transmitter flange. Use the four Installation Procedure manifold bolts for alignment.
  • Page 40 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 The manifold valves are now in the proper configuration for zeroing the transmitter. To return the transmitter to Drain/ service, close the equalizing valve(s) first. Drain/ Vent Vent Valve...
  • Page 41: Safety Messages

    • Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. NOTE The Rosemount 3051S Wireless and all other wireless devices should be installed only after the 1420 Wireless Gateway has been installed and is functioning properly.
  • Page 42: Network Status

    August 2007 NETWORK STATUS If the Rosemount 3051S Wireless was configured with the Network ID and Join Key and sufficient time for network polling has passed, the transmitter should be connected to the network. To verify connectivity, open the 1420 Wireless Gateway’s integral web interface and navigate to the...
  • Page 43 Explorer>Status page. This page will show whether the device has joined the network and if it is communicating properly. If the Rosemount 3051S Wireless was configured with the Network ID and Join Key and sufficient time for network polling has passed, the transmitter will be connected to the network.
  • Page 44 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Troubleshooting The most common cause of incorrect operation is incorrect configuration of the Network ID and Join Key. The Network ID and Join Key in the device must match that of the 1420 Wireless Gateway. The Network ID and Join Key may be obtained from the 1420 Wireless Gateway on the Setup>Network>Settings page on the web server.
  • Page 45: Overview

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Section 5 Operation and Maintenance Overview ........page 5-1 Calibration .
  • Page 46: Sensor Trim Overview

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Table 5-1. Recommended Calibration Tasks Transmitter Bench Calibration Tasks Field Calibration Tasks 1. Set output configuration parameters: 1. Reconfigure parameters if necessary. 3051S 2CD 3051S 2CG a. Set the % range points.
  • Page 47: Zero Trim

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Sensor trim is a two-point sensor calibration where two end-point pressures are applied, and all output is linearized between them. Always adjust the low trim value first to establish the correct offset. Adjustment of the high trim value provides a slope correction to the characterization curve based on the low trim value.
  • Page 48: Recall Factory Trim-Sensor Trim

    1. Click Next to acknowledge the warning. 2. Select Finish to acknowledge the method is complete. Compensating for The Rosemount 3051S Wireless Range 4 and 5 pressure transmitters require a special calibration procedure when used in differential pressure Line Pressure applications.
  • Page 49 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Applying high static pressure to the 3051S Wireless Range 4 and Range 5 pressure transmitters causes a systematic shift in the output. This shift is linear with static pressure; correct it by performing the “Sensor Trim”...
  • Page 50: Lcd Screen Messages

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 LCD SCREEN MESSAGES Startup Screen The following screens will display when the battery is first connected to the Rosemount 3051S Wireless. Sequence X X X X X All Segments On: used to visually determine if...
  • Page 51: Diagnostic Button Screen Sequence

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 S N S R SV Screen - sensor temperature value 2 5. 0 0 d e g c D E V TV Screen - feature board temperature value 2 5. 2 5...
  • Page 52: Network Diagnostic Status Screens

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 i d - X X Device Identification: used to determine Device ID X X X X X X n e t w k Diagnostic Button Screen 3: assuming the device...
  • Page 53 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Diagnostic Button Screen 4.2: the device has received the ACTIVATE command from the 1420, n e t w k but is in the process of being configured to the...
  • Page 54: Device Diagnostic Screens

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Diagnostic Button Screen 4.7: the device n e t w k synchronized to a network s y n c Diagnostic Button Screen 4.8: the device will n e t w k...
  • Page 55 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 P R E S S PV Screen - process pressure value 5 8. 0 P S I S N S R SV Screen - sensor temperature value 2 5. 0 0...
  • Page 56 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 A b c d e Diagnostic Button Screen 1 - Tag: user entered tag which is 8 characters long - will not display if all characters are blank f g h Diagnostic Button Screen 2: the device’s identifier...
  • Page 57 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Diagnostic Button Screen 9.1: configuration of the transmitter is invalid such that critical operation of c o n f g the device may be affected - check the extended...
  • Page 58 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 5-14...
  • Page 59: Overview

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Section 6 Troubleshooting Overview ........page 6-1 Safety Messages .
  • Page 60 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Table 6-1. Rosemount 3051S Wireless troubleshooting table Symptom Corrective Actions Transmitter will not respond to changes in Check test equipment applied pressure Check impulse piping or manifold for blockage...
  • Page 61: Disassembly Procedures

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 DISASSEMBLY PROCEDURES Remove from Service Be aware of the following: • Follow all plant safety rules and procedures. • Isolate and vent the process from the transmitter before removing the transmitter from service.
  • Page 62: Remove Assembly

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Remove Feature The Wireless Feature Board is located in the electronics compartment. To remove the assembly, perform the following procedure. Assembly 1. Remove the housing cover opposite the field terminal side.
  • Page 63: Reassembly Procedures

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 1. Loosen the housing rotation set screw with a -inch hex wrench, then rotate back one full turn. 2. Unscrew the housing from the SuperModule. Housing Rotation Set Screw (3/32-inch allen)
  • Page 64 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 a. If the installation requires a –18 NPT mounting, use four 1.75-in. flange bolts. Go to step f. b. If the installation requires a –14 NPT mounting, use four 2.88-in.
  • Page 65: Specifications

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Appendix A Specifications and Reference Data Performance Specifications ..... . . page A-1 Functional Specifications .
  • Page 66 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Reference Accuracy Models Classic 3051S_CD, CG Ranges 2 - 4 ±0.055% of span. For spans less than 10:1, ⎛ ⎞ % of span ± 0.015 0.005 ------------- - ⎝...
  • Page 67 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Ambient Temperature Effect Models Classic 3051S_CD, CG per 50 °F (28 °C) Range 2 - 5 ± (0.0125% URL + 0.0625% span) from 1:1 to 5:1 ± (0.025% URL + 0.125% span) from >5:1 to 100:1...
  • Page 68: Functional Specifications

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Vibration Effect Less than ±0.1% of URL when tested per the requirements of IEC60770-1 field or pipeline with high vibration level (10-60 Hz 0.21mm displacement peak amplitude / 60-2000 Hz 3g).
  • Page 69 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Wireless Self-Organizing Networks Output Wireless enabled HART. Transmit Rate User selectable, 15 sec. to 60 min. Wireless Battery ® Replaceable, Intrinsically Safe Lithium-thionyl chloride battery pack with Valox enclosure. 5-year battery life at reference conditions.
  • Page 70 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Burst Pressure Limits Coplanar or traditional process flange • 10000 psig (689,5 bar). 3051S_T: • Ranges 1–4: 11000 psi (758,4 bar) • Range 5: 26000 psig (1792,64 bar) Temperature Limits Ambient –40 to 185 °F (–40 to 85 °C)
  • Page 71: Physical Specifications

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 PHYSICAL Electrical Connections SPECIFICATIONS –14 NPT. HART interface connections fixed to terminal block. Process Connections 3051S_C –18 NPT on 2 -in. centers –14 NPT and RC on 2-in.(50.8mm), 2 -in.
  • Page 72 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Reference Process Connection (Transmitter Low Side) Isolating Diaphragms 316L SST or Hastelloy C-276 Reference Flange and Adapter CF-3M (Cast version of 316L SST, material per ASTM-A743) Non-Wetted Parts Electronics Housing...
  • Page 73 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Shipping Weights for 3051S Wireless Pressure Transmitter Table A-1. SuperModule Platform weights SuperModule Platform Weight in lb. (kg) Coplanar 3.1 (1,4) In-Line 1.4 (0,6) (1) Flange and bolts not included.
  • Page 74: Dimensional Drawings

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 DIMENSIONAL DRAWINGS Dimensions are in inches (millimeters). Process adapters (option D2) and Rosemount 305 integral manifolds must be ordered with the transmitter Wireless PlantWeb Housing with In-Line and Coplanar SuperModule Platform...
  • Page 75 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Table A-6. 3051S_L Dimensional Specifications Except where indicated, dimensions are in inches (millimeters). Pipe Flange Bolt Circle Outside No. of Bolt Hole Extension O.D. Gasket Class Size Thickness A...
  • Page 76: Ordering Information

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 ORDERING INFORMATION Rosemount 3051S Series Coplanar Model Transmitter Type 3051S Scalable pressure transmitter Code Performance Class Ultra: 0.025% span accuracy, 200:1 rangedown, 10-year stability, limited 12-year warranty Ultra for Flow: 0.04% reading accuracy, 200:1 rangedown, 10-year stability, limited 12-year warranty Classic: 0.055% span accuracy, 100:1 rangedown, 5-year stability...
  • Page 77 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Flange Material Drain Vent Bolting Traditional flange –18 NPT 316 SST Hastelloy C-276 Traditional flange 316 SST 316 SST Traditional flange Hastelloy C-276 Hastelloy C-276 Traditional flange Monel 400...
  • Page 78 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Code Wireless Options - Select code from each wireless category (example: WA2WK1) Wireless Transmit Rate User Configurable Transmit Rate Operating Frequency and Protocol 2.4 GHz DSSS, HART 900 MHz FHSS, HART...
  • Page 79 (1)(26) Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output Note: Use Belden 3084A cable or equivalent. Contact an Emerson Process Management representative for additional information. (1)(26) Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output (1)(26) Remote mount LCD display and interface, 100 ft.
  • Page 80 (22) Valid when SuperModule Platform and housing have equivalent approvals. (23) Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative for additional information. (24) Requires 316L SST wetted materials, glass-filled TFE O-ring (standard), and Process Connection code E12 or F12.
  • Page 81: Rosemount 3051S Series In-Line

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Rosemount 3051S Series In-Line Model Transmitter Type 3051S Scalable pressure transmitter Code Performance Class Ultra: 0.025% span accuracy, 200:1 rangedown, 10-year stability, limited 12-year warranty Classic: 0.055% span accuracy, 100:1 rangedown, 5-year stability...
  • Page 82 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Code Options PlantWeb Control Functionality (11) OUNDATION fieldbus Advanced Control Function Block Suite PlantWeb Diagnostic Functionality (11) OUNDATION fieldbus Diagnostics Suite (12) HART Diagnostics Suite PlantWeb Enhanced Measurement Functionality...
  • Page 83 (16) Valid when SuperModule Platform and housing have equivalent approvals. (17) Limited availability depending on transmitter type and range. Contact an Emerson Process Management representative for additional information. (18) Requires 316L SST wetted materials and Process Connection code E11 or G11.
  • Page 84: Rosemount 3051S Series Liquid Level

    Rosemount 3051S Wireless Series August 2007 Rosemount 3051S Series Liquid Level Select either FF diaphragm seal type (see “Flush Flanged Seal” on page A-21) or for EF diaphragm seal type (see “Extended Flanged Seal” on page A-22) and then finish this selection by choosing transmitter options.
  • Page 85: Seal Options (Page

    (8) Available with output code A only. Available approvals are FM Intrinsically Safe, Non-Incendive (option code I5), ATEX Intrinsically Safe (option code I1), or IECEx Intrinsically Safe (option code I7). Contact an Emerson Process Management representative for additional information. (9) Not recommended for use with spiral wound metallic gaskets (see 1199 product data sheet, document 00813-0100-4016 for additional options).
  • Page 86: Transmitter Options Continued From Page

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Extended Flanged Seal Code Process Connection Style Extended flanged, Ra 125-250 gasket surface Code Diaphragm Seal Size (High Side) 3-in./DN 80, 2.58-in. diaphragm 4-in./DN 100, 3.5-in. diaphragm Code Flange Rating (High Side)
  • Page 87 (6)(11) Remote mount LCD display and interface, no cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output Note: Use Belden 3084A cable or equivalent. Contact an Emerson Process Management representative for additional information. (6)(11) Remote mount LCD display and interface, 50 ft. (15 m) cable; PlantWeb housing, SST bracket, requires 4-20 mA / HART output (6)(11) Remote mount LCD display and interface, 100 ft.
  • Page 88 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 Calibration certificate and tamper evident seal Material traceability certification per EN 10204 3.1.B (5)(12) Certificate of FMEDA Data Terminal blocks (13) Transient terminal block (14) ® Terminal block with WAGO...
  • Page 89: Wireless Certifications

    RF spectrum. Nearly every country requires Compliance this type of product certification. Emerson is working with governmental agencies around the world to supply fully compliant products and remove the risk of violating country directives or laws governing wireless device usage. To see which countries our devices have received certification for use in, see www.rosemount.com/smartwireless.
  • Page 90: Hazardous Locations Certifications

    Information contacting an Emerson Process Management representative. ATEX Directive (94/9/EC) Emerson Process Management complies with the ATEX Directive. European Pressure Equipment Directive (PED) (97/23/EC) Models 3051S_CA4; 3051S_CD2, 3, 4, 5; (also with P9 option) Pressure Transmitters — QS Certificate of Assessment - EC No.
  • Page 91: European Certifications

    Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 European Certifications ATEX Intrinsic Safety Certificate No.: BAS01ATEX1303X II 1G Ex ia IIC T4 (T = -60 °C to 70 °C) For use with Rosemount Battery P/N 00753-9220-XXXX only...
  • Page 92 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007...
  • Page 93 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 NOTES...
  • Page 94 Reference Manual 00809-0100-4802, Rev BA Rosemount 3051S Wireless Series August 2007 NOTES...
  • Page 96 August 2007 Standard Terms and Conditions of Sale can be found at www.rosemount.com\terms_of_sale The Emerson logo is a trade mark and service mark of Emerson Electric Co. Rosemount and the Rosemount logotype are registered trademarks of Rosemount Inc. SuperModule and Coplanar trademarks of Rosemount Inc.

Table of Contents