Setup Mode
4-5-3-3

Set_Permanent_Configuration

Function
Command Code
Command Argument 1
Command Argument 2
Command Status
Command Return Value
Example
Send 'No_Command'
Send Command
Store the ID code and I/O code for a projected slave as permanent
configuration data in the master's non-volatile memory.
3 (
)
0011
Slave address (2 digits BCD)
Permanent Configuration Data for slave [Command Argument 1].
1 byte hexadecimal code, representing I/O Code and ID Code.
15 14 13 12 11 10 9
IR m+1
See Appendix B, AS-Interface Slave Profiles, for a list of ID codes and I/O
codes.
1
Command processed.
2
Error in processing the command
(invalid argument value or EEPROM write error).
other
Master is busy
Not applicable (set to 00)
Define the projected configuration data for the slave with address 23 as a
standard 2-input, 2-output slave. (I/O Code 3, ID Code 0)
Command
IR101
IR100
-
-
-
-
-
-
0 2
-
-
3 0
2 3 3 2
8
7
6
5
4
3
2
I/O
ID
Response
IR001
X X X D Master in Setup Mode
(X = previous data)
0 0 0 D Master Ready
0 0 1 D OK
Section 4-5
1
0
ID Code
I/O Code