4-5-3-2

Get_Permanent_Configuration

Function
Command Code
Command Argument 1
Command Argument 2
Command Status
Command Return Value
Example
Send 'No_Command'
Send Command
38
Read the ID code and I/O code of a slave from the permanent configuration
data in the master's non-volatile memory.
1 (
)
0001
Slave address (2 digits BCD).
Not required.
1
Command processed, and Return Value is valid.
2
Error in processing the command
(invalid argument value or EEPROM read error).
other
Master is busy.
Permanent Configuration Data for slave [Command Argument 1].
1 byte hexadecimal code, representing I/O Code and ID Code.
15 14 13 12 11 10 9
IR n
I/O
See Appendix B, AS-Interface Slave Profiles, for a list of ID codes and I/O
codes.
Read projected configuration data of the slave with address 18.
Command
IR101
IR100
-
-
-
-
-
-
0 2
-
-
-
-
1 8 1 2
8
7
6
5
4
3
ID
0
0
0
1
Response
IR001
X X X D Master in Setup Mode
0 0 0 D Master Ready
B 1 1 D I/O Code=B, ID Code =1
Section 4-5
2
1
0
1
Setup Mode
Command Status = OK
ID Code
I/O Code
(X = previous data)
(Dual actuator w/ feedback)