Setup Mode
IR m.01
Mode Control Bit
0
Standard Modes
Requests the master to operate in Configuration / Protected
Mode, depending on the position of the MOD switch.
1
Setup Mode
To enter Setup Mode, set this bit to 1, i.e. set the least
significant digit of IR m to 2.
If the MOD switch (DIP switch 5) is OFF, the Unit will enter
Setup Mode. If the MOD switch is ON, the Unit will remain in
Protected Mode.
Check the Mode Flag in the Response area to see if the
master actually is in Setup Mode, before issuing commands.
As long as the Mode Flag is not set ON, the Command Code
and Command Arguments will be interpreted as output data
for slaves 1 to 5.
IR m.04~
Command Code
IR m.07
In Setup mode, the following single-digit command codes are
valid:
0
No Command
Setting the Command Code to 0 prepares the master for the
next command. Command Code 0 MUST be issued before
each command.
1
Get_Permanent_Configuration
Returns the master's permanent configuration data for one
slave address.
3
Set_Permanent_Configuration
Sets the master's permanent configuration data for one
slave address.
5
Read_Actual_Configuration
Returns the configuration data from an actual slave con-
nected to the AS-Interface network.
7
Change_Slave_Address
Changes the address of an actual slave connected to the
AS-Interface network.
9
Get_Permanent_Parameter
Returns the master's permanent parameter data for one
slave address.
B
Set_Permanent_Parameter
Sets the master's permanent parameter data for one slave
address.
D
Read_Parameter
Returns the parameter data from an actual slave connected
to the AS-Interface network.
F
Write_Parameter
Changes the parameter data of an actual slave connected to
the AS-Interface network.
The master will ignore any Command Code not included above.