PLC Settings

4-1 PLC Settings

Example
26
In principle, the CQM1-ARM21 requires no special preparation in the CQM1
PLC system. However, to allow an AS-Interface configuration larger than 23
slaves, the Unit will need to occupy 8 IR words as input area, plus 8 IR words
as output area. With the 16 binary inputs already available in each CQM1
CPU, this would exceed the CPU's maximum of 16 I/O words (256 I/O points).
The full extent of the ARM21's I/O capacity is currently only supported by the
following CPU models:
CQM1-CPU41-EV1-NL
CQM1-CPU42-EV1-NL
CQM1-CPU43-EV1-CE
CQM1-CPU44-EV1-NL
CQM1-CPU45-EV1-NL
Produced after 01-04-1999 at OMRON Manufacturing of the Netherlands.
Lot No. 01 4 9 N
With the above models, support for the CQM1-ARM21's I/O range can be
activated by setting the following code in the CPU's PC Setup area:
DM6604 =
This code will allow the CQM1-ARM21 to access 2 additional IR words, above
the CPU's normal limitation of 16. This means that apart from the built-in
inputs of the CPU and a full-configuration AS-Interface master unit, one
additional I/O unit can be mounted.
CQM1-CPU41 with OD215 (8-point out) and ARM21 (maximum allocation)
INPUTS
15...........0
IR000
IR001
IR002
IR003
IR004
IR005
IR006
IR007
IR008
PS
CPU41
DM6604
= A51F
A
5
1
F
Section 4-1
OUTPUTS
15...........0
IR100
IR101
IR102
IR103
IR104
IR105
IR106
IR107
IR108
free work bits