Overall Specifications - Omron CQM1-ARM21 Operation Manual

As-interface master unit
Table of Contents

Advertisement

Overall Specifications

3-1 Overall Specifications

Model code
Max. number of units per CPU
Master Unit mounting position
Settings
Displays
External connectors
No. of DM settings
No. of IR words
Max. No. of Slaves per Master
Unit
Status information in PLC
Communication specification
Network configuration
Current consumption
Storage temperature
Operating temperature
Operating humidity
Conformance to EMC- and
environmental standards
Weight
18
CQM1-ARM21
One
Recommended
: rightmost I/O unit position of the CQM1 system
Switches:
: IR channel allocation
Operation Mode (Protected/Configuration)
Store Configuration
Unit status
: RUN
ERR
Network status
: APF
CER
AUP
CM
Slave status
: 0~15, +16
2 x ASI+, 2 x ASI-, M3 screw terminals, detachable terminal block.
1 words of unit setup information (DM 6604)
Switch selectable.
Minimum: 3 words in + 3 words out
Switch selectable.
With minimum IR words : 11 slaves
Operation Mode flag
System Error flag
Normal Operation flag
Configuration OK flag
European Standard EN 50295.
AS-Interface Complete Specification V 2.04.
AS-Interface Master Profiles V 1.5, profile M0.
Prüfungsordnung für AS-Interface Master V 1.1.
Certification No. 22701
Built-in configurator functions:
Get_Permanent_Configuration
Set_Permanent_Configuration
Read_Actual_Configuration
Change_Slave_Address
maximum 300 mA at 5 V DC (from the PLC power supply)
maximum 100 mA at 30.5 V DC (from the AS-Interface line)
-20 to +75°C
0 to +55°C
10% to 90% (non-condensing)
EN 50081-2
EN 61131-2
Approx. 200 g including front cover and terminal block
(green LED)
Startup, Normal operation
(red LED)
Failure, illegal operation
(red LED)
AS-Interface Power Fail
(red LED)
Configuration Error
(yellow LED)
Auto-programming available
(yellow LED)
Configuration Mode
(yellow LEDs)
Slave configured / active
Maximum: 8 words in + 8 words out
With maximum IR words : 31 slaves
Get_Permanent_Parameter
Set_Permanent_Parameter
Read_Parameter
Write_Parameter
Section 3-1