Siemens SIMOCODE 3UF Programming And Operating Manual page 81

Table of Contents

Advertisement

2. Output of the Effective Motor Current - only part of the motor current range (overload
range).
The Motor Current of a motor ranges from 0 to 8 A.
The Rated Current I
The parameterized Set Current I
Rated Current I
a pointer instrument via the Analog Module Output.
In SIMOCODE pro, representation of the effective phase currents or the maximum
current (current IL_1, IL_2, IL_3, max. current I_
a percentage of the parameterized Set Current I
– 0 A motor current corresponds to 0 % of I
– 8 A motor current corresponds to 400 % of I
– The smallest unit for the effective motor current in SIMOCODE pro is 1 %.
As a result,
– the "start value of value range (CiR)" to be selected is: 100
– the "end value of value range (CiR)" to be selected is: 400.
When the parameterized "output signal" = 0 - 20 mA:
– 100 % Motor Current corresponds to: 0 mA at the Analog Module Output
– 400 % Motor Current corresponds to: 20 mA at the Analog Module Output.
When the parameterized "Output Signal" = 4 - 20 mA:
– 100 % Motor Current corresponds to: 4 mA at the Analog Module Output
– 400 % Motor Current corresponds to: 20 mA at the Analog Module Output.
3. Output of any analog value from the automation system, cyclically via PROFINET.
1 word (2 byte) can be cyclically transmitted from the automation system to SIMOCODE
pro via PROFINET. Any value can be output as a 0/4 to 20 mA signal by directly
connecting this cyclic control word from PROFINET to the Analog Module Output. If the
transmitted value is in S7 Format (0 to 27648) it must be taken into consideration when
parameterizing:
As a result,
– the "start value of value range (CiR)" to be selected is: 0
– the "end value of value range (CiR)" to be selected is: 27648.
When the parameterized "output signal" = 0 - 20 mA:
– 0: 0 mA at the analog module output
– 27648: 20 mA at the analog module output.
When the parameterized "output signal" = 4 - 20 mA:
– 0: 4 mA at the Analog Module Output
– 27648: 20 mA at the Analog Module Output.
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
of the motor at nominal load is 2 A.
N
in Device Integration Manager corresponds to the
s
(2 A). However, only the overload range (2 A - 8 A) is to be displayed on
N
11.5 Analog Module Outputs
) corresponds to the selected range as
max
:
s
s
s
Outputs
81