Online Settings and Displays
17.11 Warnings
Indication
Warning level P>
Warning level P<
Warning level U<
Warning level Cos-Phi<
Warning level 0/4-20 mA>
Warning level 0/4-20 mA<
No. of starts>
Just one start possible
No start possible
Motor operating hours >
Motor stop time >
162
Meaning/Possible cause/Acknowledgement/Error processing
The real power of the motor has overshot theWarning level.
Check the application which is driven by the motor.
Further information: Active Power Monitoring (Page 55).
The real power of the motor has undershot the Warning level.
Check the application which is driven by the motor.
Further information: Active Power Monitoring (Page 55).
The voltage in the motor feeder has undershot the Warning level.
Possible causes:
Undervoltage in the network
Fuse has tripped.
Check the motor feeder.
Further information: Voltage Monitoring (Page 52).
The power factor has undershot the Warning level.
Possible cause: The motor is operated without a load.
Check the application which is driven by the motor.
Further information: Cos-Phi Monitoring (Page 54).
The measured value on the analog input has overshot the
Warning level.
Check the measuring station.
Further information: 0/4-20 mA Signal Monitoring (Page 60).
The measured value on the analog input has undershot the
Warning level.
Check the measuring station.
Further information: 0/4-20 mA Signal Monitoring (Page 60).
The permitted number of starts in the monitoring time frame was
exceeded. The next start should not be carried out until the
interlocking time has expired.
Further information: Monitoring the Number of Starts (Page 64).
The start after the next one should not be carried out until the
interlocking time has expired.
The permitted number of starts in the monitoring time frame was
achieved. The next start should not be carried out until the
interlocking time has expired.
Acknowledge with "Reset".
The configured limit value for the motor operating hours has been
exceeded.
Implement the maintenance measures planned for the feeder.
The configured limit value for the stopped time has been
exceeded.
Implement the maintenance measures planned for the feeder. If
possible, switch on the feeder.
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
SIMOCODE PRO V PN FDI