Indication
DM-F Safety-oriented tripping
Monitoring - interval for mandatory
testing
DM-F Local o.k.
PROFIsafe active
DM-F Local configuration mode
DM-F Local actual configuration
fault
DM-F Local waiting for start-up test The DM-F Local is in the "Waiting for start-up test" state.
DM-F incorrect PROFIsafe address
or incorrect PROFIsafe
Status - Enabling circuit closed
Module supply voltage is not
present
Initialization module write-protected The initialization module is completely write-protected.
Initialization module write-
protected, parameter changes not
allowed
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Meaning/Possible cause/Acknowledgement/Error processing
The DM-F Local / DM-F PROFIsafe have tripped the enabling
circuit for safety reasons.
The motor can only be switched on again after the DM-F
module enabling circuits have been closed.
Further information: See Safety-oriented tripping.
The DM-F Local / DM-F PROFIsafe enabling circuits have not
been opened and closed again within the configured time
period.
The function of the enabling circuit relay contacts can only be
tested when they are switched.
Further Information: See monitoring - interval for mandatory
testing.
The DM-F Local is ready for operation.
The DM-F PROFIsafe is in the "PROFIsafe active" state.
The DM-F PROFIsafe is in "Configuration mode".
Please complete the configuration.
The effective configuration of the DM-F Local does not
correspond to the parameterized set configuration.
Please check whether the effective configuration corresponds to
the parameterized set configuration and correct the effective
configuration as necessary by setting the DIP switches or
correct the parameterized set configuration.
The specified parameters of the PROFIsafe profile are faulty, or
the specified PROFIsafe address does not correspond to the
configuration.
Check the PROFINET/PROFIsafe parameters of SIMOCODE
pro that were set on the controller.
The DM-F Local / DM-F PROFIsafe enabling circuits are closed.
Supply voltage on the DM-F is too low or not present.
Please check whether the terminals have been wired
correctly.
The DM-F module might be defective. Replace the module.
Deactivate write protection of the initialization module.
The initialization module is completely write-protected.
Reparameterization of SIMOCODE pro is denied because the
initialization module is write-protected.
Deactivate the write protection of the initialization module.