Monitoring Functions
9.1 Earth Fault
Response at warning level
Here you can set how SIMOCODE pro should respond if the warning level is undershot.
Response
Disabled
Signaling
Warning
Tripping
Delay
Preset
Additional delay of the residual current transformer delay
1)
Hysteresis
Here you can set the hysteresis for the earth-fault current:
Hysteresis earth-fault current
Preset
Response at sensor fault
Here you can set how SIMOCODE pro should respond to a sensor fault:
Response
Disabled
Signaling
Warning
Tripping
48
Warning level
X
X
X
-
0 - 25.5 s
0.1 s
0 - 15% of the level value in 1% increments
5 %