Siemens SIMOCODE 3UF Programming And Operating Manual page 41

Table of Contents

Advertisement

Parameter
Change-over pause (CiR)
Max. star time (CiR)
Note
(CiR): Change in Running
The parameters followed by (CiR) can be changed when the motor is in operation.
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Description
In the "Dahlander" and "Pole-changing starter" control
functions, switching from the fast speed to the slow one can
be delayed with the time configured. In the "Star-Delta"
control function, the change-over pause time extends the
time between switching off the star contactor and switching
on the delta contactor by the time configured.
Default: 0.00 s.
For the "Star-delta Starter" or the "Star-delta Reversing
Starter" control function: Time-dependent switching from
star to delta.Max. star time: 0 - 255 s (default: 20 s).
Motor Control
8.3 Control Function
41