Monitoring Functions
9.5 Active Power
Warning Level
• P> (upper limit)
• P< (lower limit)
Trip level and warning level activity
The trip level/warning level is only effective when the motor is running, the start-up
procedure has been completed and there is no Test Position Feedback (TPF) (run+).
Response, Delay (CiR) at trip level:
Here you can set:
● how SIMOCODE pro should respond if the set Trip Level is either undershot or overshot
● the delay time.
Response
Disabled
Signaling
Warning
Tripping
Delay
Preset
Response, Delay (CiR) at warning level
Here you can set:
● how SIMOCODE pro should respond if the set warning level is overshot
● the delay time.
Response
Disabled
Signaling
Warning
Tripping
Delay
Preset
56
0 to 4294967.295 kW
Trip level
X
X
-
X
0 to 25.5 s
0.5 s
Warning level
X
X
_
-
0 to 25.5 s
0.5 s
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001