Motor Control
8.3 Control Function
Parameter
DM-F LOCAL/DM-F PROFIsafe -
separate function from the control
function
Type of consumer load
38
Description
• Deactivated:
A safety-oriented tripping via the DM-F module also
affects the SIMOCODE pro control function, so that
the contactor control is always tripped, too.
This setting is selected for applications where a
safety-oriented tripping directly affects the motor
controlled by SIMOCODE pro.
• Activated:
A safety-oriented tripping via the DM-F module does
not affect the SIMOCODE pro control function, so
that the contactor control is not tripped.
This setting is selected for applications where a
safety-oriented tripping does not affect the motor
controlled by SIMOCODE pro.
You can choose between:
• Motor and
• Resistive load (e.g. heating)
Because generally no overcurrent flows in a resistive
load during switching, the "Start Active" status is not
signaled. In this case, the start-up override does not
occur for the "signaling", "warning" and "tripping"
functions.