Device Configuration
5.2 Module Configuration
● Temperature module 1/2. Choose here whether or not a temperature module is to be
used for temperature monitoring (e.g., for monitoring the motor windings, motor bearings,
coolant temperature, or gearbox temperature). Temperature module 2 can only be
activated if temperature module 1 has been configured.
● Analog module 1/2. Choose here whether or not the analog signals of a transducer
(standard output signal 0/4-20 mA) are to be monitored. Analog module 2 can only be
activated if analog module 1 has been configured.
● Earth fault module: Select here whether the external earth-fault monitoring is to be used
via a residual current transformer and earth-fault module.
● If yes, select
– The 3UF7500 earth-fault module (in conjunction with the 3UL22 residual current
– The 3UF7510 earth-fault module (in conjunction with the 3UL23 residual current
● Initialization module: This can be permanently installed in the switchgear and enable
backup of all parameters of a system and completely automatic transmission to a new
system, e.g. device replacement.
Note
The DM-F Local and DM-F PROFIsafe failsafe digital modules can be activated from the
following firmware versions onwards:
• Pro V PN: V1.0.
Note
The earth fault module 3UF7510 can be activated from the following firmware versions
onwards:
• Pro V PN: V1.1.
18
transformer)
transformer).
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
SIMOCODE PRO V PN FDI