Indication
Trip level P>
Trip level P<
Trip level U<
Trip level Cos-Phi<
Analog module 1/2 Trip level
0/4-20 mA>
Analog module 1/2 Trip level
0/4-20 mA<
No. of starts>
Trip level T>
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
Meaning/Possible cause/Acknowledgement/Error processing
The real power of the motor has overshot the trip level.
Check the application which is driven by the motor.
Further information: Active Power Monitoring.
The real power of the motor has undershot the trip level.
Check the application which is driven by the motor.
Further information: Active Power Monitoring.
The voltage in the motor feeder has undershot the trip level.
Possible causes:
Undervoltage in the network
Fuse has tripped.
Check the motor feeder.
Further information: Voltage Monitoring.
The power factor has undershot the trip level.
Possible cause: The motor is operated without a load.
Check the application which is driven by the motor.
Further information: Cos-Phi Monitoring.
The measured value on the analog input has overshot the trip
level.
Check the measuring station.
Further information: 0/4-20 mA Signal Monitoring.
The measured value on the analog input has undershot the
trip level.
Check the measuring station.
Further information: 0/4-20 mA Signal Monitoring.
The permitted number of starts in the monitoring time frame
was exceeded. The next start should not be carried out until
the interlocking time has expired.
Further information: Monitoring the Number of Starts.
Temperature module 1/2 Trip level 0/4-20 mA< - Trip level
overshot.
Check the temperature measuring station.
Further information: Analog Temperature Monitoring.