Inputs
10.1 Digital Inputs
Digital Module Inputs
SIMOCODE pro has two DM Inputs function blocks, each with four grouped binary inputs
with common potential. You can connect e.g. the buttons for a Local Control Station to the
inputs. These signals can be further processed in SIMOCODE pro by internally wiring the
sockets of the DM Inputs function blocks.
Note
The DM Inputs function blocks can only be used if the respective Digital Module (DM) is
connected and configured in the device configuration!
Note
When using the DM-F Local and DM-F PROFIsafe failsafe digital modules, the input signals
can be used as non-safety-oriented information.
Each DM Inputs function block consists of:
● Input terminals located on the outside of the Digital Module, corresponding to the sockets
DM Input 1 to DM Input 4.
● Sockets in SIMOCODE pro that can be connected to any plugs, e.g. to the Control
Stations function block.
1 DM1 inputs function block and 1 DM2 inputs function block are available for the
SIMOCODE pro V PN basic units.
Application examples
Digital Modules allow the number of binary inputs and outputs on Basic Unit 2 to be
increased in increments. SIMOCODE pro V can thus be extended to a maximum of twelve
Binary Inputs and seven Binary Outputs. By allocating accordingly, input signals can be used
to activate, for example, function blocks such as "Reset" or "External Fault".