Trip level (CiR), warning level (CiR)
You can parameterize two different response levels (trip level, warning level) for earth-fault
current monitoring.
If the earth-fault current exceeds the set response level, the earth-fault monitoring function
responds.
Trip level:
Warning level:
Note
(CiR): Change in Running
The parameters followed by (CiR) can be changed when the motor is in operation.
Active status trip level, warning level
Unless deactivated, this function is always active, independent of whether the motor is
running or not (operating state "ON").
Here you can specify in which motor operating states the trip level/warning level is to be
active.
always (on)
if motor is running, except TPF (run)
if motor is running, except TPF, with
startup override (run+)
Response at trip level
Here you can set how SIMOCODE pro should respond if the trip level is undershot.
Response
Signaling
Warning
Tripping
Delay
Preset
Additional delay of the residual current transformer delay.
1)
SIMOCODE PRO V PN FDI
Programming and Operating Manual, 05/2020, A5E44499659002A/RS-AA/001
30 mA ... 40 A in 10 mA increments (default setting: 1000 mA)
20 mA ... 40 A in 10 mA increments (default setting: 500 mA)
trip level/warning level always active, regardless of
whether the motor is running or at a standstill
trip level/warning level only active if motor running.
trip level/warning level only active if motor running
and start procedure completed.
Trip level
X
-
X
0 - 25.5 s
1)
0.5 s
Monitoring Functions
9.1 Earth Fault
47