5 Installation Procedure

Setting Station Address

Set F6-10 [CC-Link Node Address] to a station address (Range 1 to 64) unique to the
network. If you set F6-10 = 0, the L.ERR light will turn ON and an AEr [Station Address
Setting Error] will occur.
5
Installation Procedure

Section Safety

DANGER
energized drive. Before servicing, disconnect all power to the equipment and wait for the time specified on
the warning label at a minimum. The internal capacitor stays charged after the drive is de-energized. The
charge indicator LED extinguishes when the DC bus voltage decreases below 50 Vdc. When all indicators
are OFF, measure for dangerous voltages to make sure that the drive is safe. If you do work on the drive
when it is energized, it will cause serious injury or death from electrical shock.
WARNING
Replace covers and shields before you operate the drive. Use the drive only as specified by the
instructions. Some figures in this section include drives without covers or safety shields to more clearly
show the inside of the drive. If covers or safety shields are missing from the drive, it can cause serious
injury or death.
WARNING
examine, replace parts, and repair the drive. If personnel are not approved, it can cause serious injury or
death.
WARNING
drive is energized. If you touch the internal components of an energized drive, it can cause serious injury
or death.
WARNING
wiring, or cause damage to the wire insulation. Damaged wires can cause serious injury or death.
WARNING
Connections that are too loose or too tight can cause incorrect operation and damage to the drive.
Incorrect connections can also cause death or serious injury from fire.
NOTICE
correct electrostatic discharge (ESD) procedures. If you do not follow procedures, it can cause ESD
damage to the drive circuitry.
NOTICE
voltage. Incorrect equipment sequencing can cause damage to the drive.
NOTICE
You can cause damage to the drive and connected equipment.
NOTICE
can cause the drive or option to function incorrectly.
NOTICE
can cause malfunction or damage to the equipment.
16
Electrical Shock Hazard. Do not examine, connect, or disconnect wiring on an
Electrical Shock Hazard. Do not operate the drive when covers are missing.
Electrical Shock Hazard. Only let approved personnel install, wire, maintain,
Electrical Shock Hazard. Do not remove covers or touch circuit boards while the
Electrical Shock Hazard. Do not use damaged wires, put too much force on the
Fire Hazard. Tighten all terminal screws to the correct tightening torque.
Damage to Equipment. When you touch the option, make sure that you observe
Damage to Equipment. Do not de-energize the drive while the drive is outputting
Do not operate a drive or connected equipment that has damaged or missing parts.
Use Yaskawa connection cables or recommended cables only. Incorrect cables
Damage to Equipment. Correctly connect the connectors. Incorrect connections
YASKAWA TOEP C730600 83A CC-Link Installation Manual