Page 1
YASKAWA AC Drive Option EtherNet/IP Technical Manual Model SI-EN3D To correctly use the product, read this manual thoroughly and keep it for easy reference, inspection, and maintenance. Make sure that the end user receives this manual. MANUAL NO. SIEP C730600 0DB...
YASKAWA products remain the responsibility of the equipment designer or end user. YASKAWA accepts no responsibility for the way its products are incorporated into the final system design. Under no circumstances should any YASKAWA product be incorporated into any product or design as the exclusive or sole safety control.
• The products and specifications described in this manual or the content and presentation of the manual may be changed without notice to improve the product and/or the manual. • Contact Yaskawa or a Yaskawa representative and provide the manual number shown on the front cover to order new copies of the manual. DANGER Do not ignore the safety messages in this manual.
Note: • Refer to the option package labeling in the field designated “PRG (four digit number)” to identify the option software version. • For Yaskawa customers in the North or South America regions: If your product is not listed in Table 2.1, refer to the web page below to confirm this manual is correct for your product.
After receiving the option package: • Make sure that the option is not damaged and no parts are missing. The Yaskawa warranty does not include damage from shipping. Contact your sales outlet if there is damage to the option or other parts.
The communication modular connector CN1 on the option is a modular dual RJ45 female connector designated port 1 and port 2. Port 1 and port 2 are the connection points for a customer-supplied male EtherNet/IP network communication cable. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
The option is online without an established connection. Communications error (fatal) The option detected a duplicate IP address. Flashing Communications time-out (non-fatal) A communications time-out occurred. Red/Green Flashing Option self-test The option is in self-test mode. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Do not operate a drive or connected equipment that has damaged or missing parts. You can cause damage to the drive and connected equipment. NOTICE Use Yaskawa connection cables or recommended cables only. Incorrect cables can cause the drive or option to function incorrectly. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
N - Connector CN5-B (Not available for communication option installation.) G - Removable tabs for wire routing O - Connector CN5-C (Not available for H - Included screws communication option installation.) Figure 5.1 Drive Components with Option YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 16
Put the LED label (B) in the correct position on the drive front cover (A). A - Drive front cover B - LED label Figure 5.3 Put the LED Label on the Drive Front Cover YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 17
• Route the option wiring inside the enclosure as shown in Figure 5.6-B. Refer to the drive manuals for more information. Note: Isolate communication cables from main circuit wiring and other electrical and power lines. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Prepare the Drive for the Option Correctly wire the drive as specified by the manual packaged with the drive. Make sure that the drive functions correctly. Refer to the drive manuals for more information. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 19
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 20
Put the LED label (B) in the correct position on the drive front cover (A). A - Drive front cover B - LED label Figure 5.10 Put the LED Label on the Drive Front Cover YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 21
Reattach the drive front cover (A) and the keypad (B). Refer to the drive manuals for more information. NOTICE Do not pinch cables between the front covers and the drive. Failure to comply could cause erroneous operation. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
This section shows the procedure to install and wire the option on a GA700 or GA800 drive. Prepare the Drive for the Option Before you install the option on a YASKAWA AC Drive GA700 or GA800, make sure that the option software version is PRG: 0345 or later.
Page 23
Refer to the drive manuals for more information. NOTICE Do not remove the LED Status Ring board cable connector. If you disconnect the LED Status Ring board, it can cause incorrect operation and damage to the drive. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 24
Note: • Replace the keypad connector then install the keypad. • Put the keypad connector tab into the holder when you install the keypad connector to the holder. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Before you install the option on an FP605 drive, make sure that the option software version is PRG: 0347 or later. Correctly wire the drive as specified by the manual packaged with the drive. Make sure that the drive functions correctly. Refer to the drive manuals for more information. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 26
Damage to Equipment. When you touch the option, make sure that you observe correct electrostatic discharge (ESD) procedures. If you do not follow procedures, it can cause ESD damage to the drive circuitry. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 27
Put the LED label (B) in the correct position on the drive front cover (A). A - Drive front cover B - LED label Figure 5.22 Put the LED Label on the Drive Front Cover YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 28
Install the option (A) into the connector (C) (HV600: CN5, FP605: CN5-A) on the drive and use the included screw (B) to put it in place. Tighten the screw to a correct tightening torque: • 0.5 N∙m to 0.6 N∙m (4.4 in∙lb to 5.3 in∙lb) YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 29
Note: Refer to Figure 5.26 for instruction about crimp terminal orientation (C) and wire routing. A - Ground wire C - Crimp terminal B - Included screw Figure 5.26 Connect the Ground Wire YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Switches implementing IGMP Snooping are strongly recommended. When IGMP Snooping is used, devices will only receive the multicast packets in which they are interested. ◆ Communication Cable Specifications Yaskawa recommends using shielded Cat5e cable. The Yaskawa warranty does not cover other cable types. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Check the back cover of these manuals. For questions, contact Yaskawa or a Yaskawa representative. Note: Download the EDS file for SI-EN3D option. The SI-EN3D will not function as a slave in the network without the appropriate EDS file. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
When you enable this parameter, d5-01 [Torque Control Selection] sets the drive to read the value as the Torque Limit value or the Torque Reference value. d5-01 = 0 [Speed Control]: Torque Limit YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 33
Sets the static/fixed Subnet Mask. Sets the most significant octet. (03E9) Note: (0 - 255) • This parameter is only effective when F7-13 = 0 [Address Mode at Startup = Static]. • All IP Addresses must be unique. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 34
–When 5: Auto/Half, port 1 is set to Auto and port 2 is set to Half. –When 6: Auto/Full, port 1 is set to Auto and port 2 is set to Full. –When 7: Full/Half, port 1 is set to Full and port 2 is set to Half. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 36
OPT SPARE 4 Shows option software version. Shows first option fault. Refer to page for more U6-98 First Fault information. Shows current option fault. Refer to page for more U6-99 Current Fault information. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
(Vendor Specific Yaskawa Electric (YE) Assy) MEMOBUS Message Input Input (Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Status Input 151 (97) Input (Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/ Torque Status Input 155 (9B) Input 166 (A6) (Vendor Specific Yaskawa Electric (YE) Assy) High Speed/Torque Status Input...
Input 101 (65) (Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Control Output Output 115 (73) (Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/Torque Control Output Output 116 (74) (Vendor Specific Yaskawa Electric (YE) Assy) High Speed/Torque Control Output Output 117 (75)
Torque Reference/Torque Limit Sets the Torque Reference when using Torque Control [d5-01 = 1]. Sets the Torque Limit when using Speed Control [d5-01 = 0]. The Torque Reference/Torque Limit are disabled when F6-06 = 0. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Torque Reference/Torque Limit Sets the Torque Limit when using Speed Control [d5-01 = 0]. The Torque Reference/Torque Limit are disabled when F6-06 = 0. ◆ MEMOBUS/Modbus Message Output (Vendor Specific Yaskawa Electric (YE) Assy) - 100 (0x64) Output Instance Word...
Refer to the MEMOBUS/Modbus Data Table in Appendix C of the Technical Manual for a list of monitor data using the MEMOBUS/ Modbus message area. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Control Output - 101 (0x65) Output Instance...
The Torque Reference/Torque Limit are disabled when F6-06 = 0. Torque Compensation Torque Compensation Sets the amount of Torque Compensation Sets in units of 0.1%. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/Torque Control Output - 115 (0x73) Output Instance Word Byte Bit 7...
Page 43
Sets the amount of Torque Compensation Sets in units of 0.1%. Analog Output 1 MEMOBUS/Modbus (0x0007) Analog Output 2 MEMOBUS/Modbus (0x0008) MEMOBUS/Modbus (0x0009) Digital Outputs Note: These values are ORed with values in byte 1. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
8 Output Assemblies (Drive Consumes) ◆ (Vendor Specific Yaskawa Electric (YE) Assy)-High Speed/Torque Control Output - 116 (0x74) The first 20 Bytes (0-19) are fixed and the next 20 Bytes can be configured using parameters F7-23 to F7-32. If an error occurs while trying to write to the dynamic parameters, the appropriate error bit in Assembly 166 will be set.
Page 45
Sets in units of 0.1%. Digital Inputs Sets digital inputs 9-12 if the drive supports them. NetRef Network sets reference NetCtrl Network sets control Analog Output 1 MEMOBUS/Modbus (0x0007) Analog Output 2 MEMOBUS/Modbus (0x0008) YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to page for more information. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 8 Byte Dynamic Output - 117 (0x75) Output Instance...
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to page for more information. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 12 Byte Dynamic Output - 118 (0x76) Output Instance...
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to page for more information. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 18 Byte Dynamic Output - 119 (0x77) Output Instance...
Modbus register. If the PPA is Input Assembly 166, then any errors occurring during a write will be flagged. Refer to page for more information. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 24 Byte Dynamic Output - 120 (0x78) Output Instance...
Page 50
0: M5/M6 OFF 1: M5/M6 ON Multi-Function Digital Output 3 This function is enabled only when H2-03 is set to F. Note: The names of the digital outputs are different for different drive series. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
= 4096 = 1000 (Hex.) Unit depends on o1-03. Output Torque Torque Actual Shows the Torque Reference. Value displays in 0.1% units. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) MEMOBUS/Modbus Message Input - 150 (0x96) Input Instance Word Byte Bit 7 Bit 6...
Refer to the MEMOBUS/Modbus Data Table in Appendix C of the drive Technical Manual for a list of monitor data using the MEMOBUS/Modbus message area. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Status Input - 151 (0x97) Input Instance...
Actual Output Current Monitors drive output current. Current Actual Unit: 0.1 A Unit is not affected by Current Scale CS. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/Torque Status Input - 155 (0x9B) Input Instance Word Byte Bit 7...
Page 56
Speed Agree Speed Agree 0: - 1: Speed actual at speed reference Ready Ready 0: Not Ready 1: Ready Alarm Alarm 0: No Alarm 1: Alarm Faulted Faulted 0: No Fault 1: Fault YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
PG Pulse Count for Channel 2 U6-19 ◆ (Vendor Specific Yaskawa Electric (YE) Assy) High Speed/Torque Status Input - 166 (0xA6) If an error occurs while trying to read from the dynamic parameters, the appropriate error bit in Assembly 166 will be set.
Page 59
The names of the digital outputs are different for different drive series. Terminal M3/M4 (varies by drive model) 0: M3/M4 OFF Multi-Function Digital Output 2 1: M3/M4 ON This function is enabled only when H2-02 is set to F. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 60
(Register number failure) is usually set. Table 9.3 Extended Error Codes for Assembly 116/166 Error Code Description 0x00 No Fault 0x01 Sub function code failure 0x02 Register Number 0x21 Limit check error failure 0x22 Write Failure YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Contains the data to be read from the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given Dynamic Inputs parameter means it will return the default data as defined in the table above. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 12-Byte Dynamic Input - 168 (0xA8) Input Instance Word...
Contains the data to be read from the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given Dynamic Inputs parameter means it will return the default data as defined in the table above. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 18-Byte Dynamic Input - 169 (0xA9) Input Instance Word...
Page 64
This function is enabled only when H2-02 is set to F. Note: The names of the digital outputs are different for different drive series. Multi-Function Digital Output 3 Terminal M5/M6 (varies by drive model) YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Contains the data to be read from the MEMOBUS/Modbus address defined in the given parameter. A value of 0 in the given Dynamic Inputs parameter means it will return the default data as defined in the table above. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 24-Byte Dynamic Input - 170 (0xAA) Input Instance Word...
Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0 D1000: Run Fault Reset R1000: Auto D1000: Voltage Reference (Low Byte) R1000: - D1000: Voltage Reference (High Byte) R1000: - YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Setting range: 0 - FFFF (Hex.) R1000: - Example: setting a reference of 4096 with a voltage scale of 2: Voltage reference data = 4096/2 = 1024 = 400 (Hex.) Unit depends on o1-03. R1000: - YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
D1000: - R1000: Forced Run R1000: Force run converter Fault Reset Fault Reset 0: - 1: Fault Reset Run command from network NetCtrl 0: Depends on b1-02 1: Enables the run command from network YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Example: setting a reference of 4096 with a voltage scale of 2: Voltage reference data = 4096/2 = 1024 = 400 (Hex.) Unit depends on o1-03. R1000: - ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Control Output - 101 (0x65) Output Instance Word Byte Bit 7...
The names of the digital outputs are different for different converter series. D1000: Voltage Reference D1000: Voltage Reference Sets converter voltage reference. R1000: - R1000: - ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/Torque Control Output - 115 (0x73) Output Instance Word Byte Bit 7 Bit 6...
Note: These values are ORed with values in byte 1. ◆ (Vendor Specific Yaskawa Electric (YE) Assy)-High Speed/Torque Control Output - 116 (0x74) The first 20 Bytes (0-19) are fixed and the next 20 Bytes can be configured using parameters F7-23 to F7-32. If an error occurs while trying to write to the dynamic parameters, the appropriate error bit in Assembly 166 will be set.
Page 72
0: Stop 1: Auto Run D1000: - D1000: - R1000: Force run converter R1000: Forced Run 0: Stop 1: Force Run Terminal S3 Function Input Multi-Function Input 3 0: Terminal S3 Function [H1-03] OFF YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 73
Contains the data to be written to the MEMOBUS/Modbus address defined in the given parameter. Programmable Bytes A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/Modbus register. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
10 Output Assemblies (Converter Consumes) ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 8 Byte Dynamic 2 Output - 117 (0x75) Output Instance Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0...
A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/Modbus register. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 12 Byte Dynamic 4 Output - 118 (0x76) Output Instance ...
A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/Modbus register. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 18 Byte Dynamic 7 Output - 119 (0x77) Output Instance ...
A value of 0 in the given parameter means it is not used, therefore the value received for this given parameter will not be written to any MEMOBUS/Modbus register. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 24 Byte Dynamic 10 Output - 120 (0x78) Output Instance ...
Page 78
This function is enabled only when H2-02 is set to F. Note: The names of the digital outputs are different for different converter series. Terminal M5/M6 (varies by converter model) Multi-Function Digital Output 3 0: M5/M6 OFF YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Running During Regenerative Operation During Regenerative Operation Ready Ready 0: Not Ready 1: Ready Run command is from network NetCtrl 0: Run command is not from network 1: Run command is from network YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
For example, when output voltage of 1024 with a voltage scale of 2: Voltage actual data = 1024 x 2 = 4096 = 1000 (Hex.) ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Speed/Torque Status Input - 151 (0x97) Input Instance Word...
D1000: Current Actual Unit: 0.1 A R1000: - Unit is not affected by Current Scale CS. R1000: - ◆ (Vendor Specific Yaskawa Electric (YE) Assy) Extended Speed/Torque Status Input - 155 (0x9B) Input Instance Word Byte Bit 7 Bit 6...
Page 83
This function is enabled only when H2-02 is set to F. Note: The names of the digital outputs are different for different converter series. Multi-Function Digital Output 3 Terminal M5/M6 (varies by converter model) YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Sets digital inputs 9-12 if the drive supports them. ◆ (Vendor Specific Yaskawa Electric (YE) Assy) High Speed/Torque Status Input - 166 (0xA6) If an error occurs while trying to read from the dynamic parameters, the appropriate error bit in Assembly 166 will be set.
Page 85
During Run - Operation Ready 0: Not Ready 1: Ready Ready Ready 0: Not Ready 1: Ready Alarm Alarm 0: No Alarm 1: Alarm Faulted Faulted 0: No Fault 1: Fault 0: - 1: oPExx Undervoltage YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 86
Monitor parameter U1-25 F7-41 Not Used F7-42 Not Used Possible extended error codes are listed in Table 11.1 Table 11.2. If an error occurs, extended error code 0x02 (Register number failure) is usually set. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
F7-39 Byte 16 F7-40 Byte 17 F7-41 Byte 18 F7-42 Byte 19 ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 8-Byte Dynamic Input 2 - 167 (0xA7) Input Instance Word Byte Bit 7 Bit 6 Bit 5 Bit 4 Bit 3...
Programmable: MEMOBUS/Modbus (0x7F) D1000: Programmable: MEMOBUS/Modbus (0x47) D1000: F7-34 Output Power Monitor parameter U1-08 R1000: F7-34 Not Used R1000: - ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 12-Byte Dynamic Input 4 - 168 (0xA8) Input Instance Word Byte Bit 7 Bit 6...
Page 89
This function is enabled only when H2-03 is set to F. Note: The names of the digital outputs are different for different converter series. Output Voltage Converter Output Voltage F7-33 Alarm Code Programmable: MEMOBUS/Modbus (0x7F) YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Run command is from network F7-39 NetCtrl 0: Run command is not from network 1: Run command is from network F7-39 Not Used ◆ (Vendor Specific Yaskawa Electric (YE) Assy) 24-Byte Dynamic Input 10 - 170 (0xAA) Input Instance Word Byte Bit 7...
Page 92
Multi-Function Digital Output 3 This function is enabled only when H2-03 is set to F. Note: The names of the digital outputs are different for different converter series. Output Voltage Converter Output Voltage YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Each unit is Serial number Option serial number. ○ Long unique Product dependent Product Name Product Name ○ String (i.e., CIMR- AA2A0004) Operation status of the drive. State 3: Drive ready ○ Byte 4: Fault YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Control Supervisor Object - 41 (Class 0x29) Note: This information applies to all products except D1000/R1000 converters. For the D1000/R1000 data for this object, refer to Control Supervisor Object 41 (Class 0x29) on page 106. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
1: Run command is from network EtherNet/IP Fault Mode Normal 2 (Vendor Specific) ○ Byte External Fault 0: - Force Fault ○ ○ Byte 0, 1 1: External Fault [EF0] Triggered by the rising edge of the signal. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
[Inversion Prevention Detection] 8000 LF2 [Output Current Imbalance] 8000 STo [Pull-Out Detection] Note: When using YASKAWA AC Drive GA500, GA700, GA800, HV600, or FP605, STPo [Motor Step-Out Detected] will be shown. 7000 PGoH [Encoder (PG) Hardware Fault] 1000 SEr [Speed Search Retries Exceeded]...
Page 99
Current Scale (-15 - +15) ○ ○ Byte -15 - +15 Sets or verifies F7-18 [EtherNet/IP Current Scale Factor]. Scale of Units for Torque Related Torque Scale (-15 - +15) ○ ○ Byte -15 - +15 Data YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
When two supervisors are on the network, the supervisor with the higher MAC address will become the supervisor and the other will become a backup supervisor. Yaskawa recommends that all devices in the ring be DLR capable. Add non-DLR devices to the ring through a DLR-capable device, such as a 3-port ETAP.
Base Energy Object 78 (Class 0x4E) on page 108 for more information about this object compatible with D1000 and R1000. ■ Services Supported Service Code No. (hex) Service Name Get Attribute Single Set Attribute Single YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
999,999,999,999 Array of 5 units of kWh. .999 signed Words STRUCT of Energy Type Specific Always 02 20 UINT Size EPATH to Base Energy Object ○ Object Path 4E 24 01 Padded EPATH YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Encapsalation Inactivity Number of seconds of inactivity ○ ○ UINT 1 s - 3600 s 120 s Timeout before TCP connection is closed. Note: “Get Attributes All” Service shall report in attribute ascending order. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
○ Byte 1: Voltage command is from network Control Mode Drive Mode ○ ○ Byte 0: Vendor Specific Control Mode Voltage read from U1-52 [DC Bus Voltage Actual ○ Word DC Bus Voltage]. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Array of 5 Odometer (kWh)]. .999 words R1000: Always 0 Regenerative power read from U9- ODOMETER Generated Energy 04 [Regenerative Power (GWh)] to ○ 999,999,999,999 Array of 5 Odometer U9-06 [Regenerative Power .999 words (kWh)]. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Get Attribute Single Set Attribute Single Yaskawa Drive Parameters object is related to the parameters or monitor of Yaskawa drives. Not compatible with EtherNet/IP compatible drives from a different company. With this Class object any drive parameter or monitor YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
2. Refer to the MEMOBUS/Modbus Data Table in the MEMOBUS/Modbus Communications chapter of the drive manual for a list of monitor data using the MEMOBUS/Modbus message area. ◆ Yaskawa Monitor/Control Object - 125 (Class 0x7D) ■ Services Supported Service Code No. (Hex.)
15 Web Interface Yaskawa Monitor/Control object is related to the parameters or monitors of Yaskawa drives. Not compatible with the EtherNet/IP compatible drives from another company. With this Class object any parameter or monitor with a MEMOBUS/Modbus address less than 0x0100 can be accessed. In this class, the most significant byte of MEMOBUS/Modbus address is always zero and the Instance ID remains at 1.
If a packet is not received in the time specified by the RPI times the Connection Timeout Multiplier, the connection is broken. O2T RPI Requested Packet Interval between the originator (PLC) and the target (drive) YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Subnet Mask Subnet Mask of the option. Gateway Address The Gateway IP Address that the option will use. MAC Address MAC Address of the option. Address Mode Either static IP address or DHCP. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Displays the MAC address of the supervisor, if it is present on the network. Beacon Interval Displays the beacon interval set by the supervisor in microseconds. Beacon Timeout Displays the beacon timeout set by the supervisor in microseconds. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
The timer helps limit the amount of emails sent regarding the same intermittent condition and helps to reduce network traffic by reducing emails about reoccurring errors. Clicking [Save Email Settings] will save the entered information into the option. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Clicking [Set] will save the given value to the given MEMOBUS/Modbus address. After a [Read] or [Set] command is given, Status will display [Waiting] while the action is being carried out, then [Read Successful] or [Write Successful] is displayed when finished. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Drive-side error codes appear on the drive keypad. Faults on page 118 lists causes of the errors and possible corrective actions. Refer to the drive Technical Manual for additional error codes that may appear on the drive keypad. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
CN5-A, CN5-B, or CN5-C. ■ Minor Faults and Alarms Code Name Causes Possible Solutions Comm. Option Parameter Not Upgraded Re-energize the drive to update the communication option CyPo Cycle Power to Active Parameters parameters. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Fault Declared Value (U6- Description 98/U6-99) No faults No faults Fatal error occurred Network sent a message to force this node to the fault state. Network Link Down 1100 No network link to option. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Factory default MAC Address programmed into the option. Note: Default MAC Address 1103 Return the option to Yaskawa or your nearest sales representative and request the setting change. Two drive monitor parameters, U6-98 [First Fault] and U6-99 [Current Fault] assist the user in network troubleshooting.
Page 121
Figure 17.2 Option Installation for CE Compliance: GA500, HV600 Figure 17.3 Option Installation for CE Compliance: FP605 Ground the largest possible surface area of the shield to the metal panel. Yaskawa recommends using cable clamps. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
• Falling foreign objects Altitude Up to 1000 m (3280 ft) Disposal ◆ Disposal Instructions Correctly dispose of the product and packing material as specified by applicable regional, local, and municipal laws and regulations. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
The wheelie bin symbol on this product, its manual, or its packaging identifies that you must recycle it at the end of its product life. You must discard the product at an applicable collection point for electrical and electronic equipment (EEE). Do not discard the product with usual waste. YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Revision History Date of Publication Revision Number Section Revised Content Addition: Information on FP605 November 2021 Revision: Reviewed and corrected entire documentation August 2020 First Edition YASKAWA SIEP C730600 0DB EtherNet/IP Technical Manual...
Page 126
Phone: +81-3-5402-4502 Fax: +81-3-5402-4580 www.yaskawa.co.jp YASKAWA AMERICA, INC. 2121, Norman Drive South, Waukegan, IL 60085, U.S.A. Phone: +1-800-YASKAWA (927-5292) or +1-847-887-7000 Fax: +1-847-887-7310 www.yaskawa.com YASKAWA ELÉTRICO DO BRASIL LTDA. 777, Avenida Piraporinha, Diadema, São Paulo, 09950-000, Brasil Phone: +55-11-3585-1100 Fax: +55-11-3585-1187 www.yaskawa.com.br...