10 Drive Start-Up Procedure
5. Remove the keypad, front cover, conduit bracket, and knock-outs. Reinstall the control bracket for non-cabinet
installations.
6. Install the motor wiring and power wiring.
7. Install the front cover and keypad.
8. Energize the drive and confirm it is ready.
9. Set the motor rated current (FLA) from the motor nameplate in E2-01.
10. Set the drive for LOCAL control and check the motor rotation direction.
The drive is prepared to run the operation.

Change Parameter Setting Values

This example shows how to change the setting value for C1-01 [Acceleration Time 1]. Do the steps in this procedure
to set parameters for the application.
1.
Push
(Home) to show the HOME screen.
Note:
• When the drive is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
• If [Home] is not shown above the
2.
Push
(Menu).
3.
Push
or
4.
Push
or
5.
Push
or
56
, push
to select [Parameters], then push
to select [C Tuning], then push
to select [C1 Accel & Decel Time], then push
(Back).
.
.
.
YASKAWA TOEPC7106171FD FP605 DRIVE INSTALLATION & PRIMARY OPERATION