6 Related Drive Parameters

6
Related Drive Parameters
These parameters set the drive for operation with the option. Make sure that the parameter
settings in this table are correct before you start network communications.
Note:
Hex.: MEMOBUS addresses that you can use to change parameters over network communication are
represented in hexadecimal numbers.
No.
Name
(Hex.)
b1-01
Frequency
Reference
(0180)
Selection 1
(For Drive)
b1-02
Run Command
Selection 1
(0181)
(For Drive,
D1000)
34
Figure 5.20 Termination Resistor Wiring
Selects the input method for frequency reference.
0 : Keypad
1 : Analog Input
2 : MEMOBUS/Modbus Communications
3 : Option PCB
4 : Pulse Train Input
Note:
• Set b1-02 = 3 [Run Command Selection 1 = Option
PCB] to use the master device and serial
communications to start and stop the drive. Set b1-01 =
3 to use the master device to control the frequency
reference of the drive.
• The default setting is different for different drives. Refer
to the instruction manual of your specific drive for more
information.
Selects the input method for the Run command.
0 : Keypad
1 : Digital Input
2 : MEMOBUS/Modbus Communications
3 : Option PCB
Note:
Set b1-02 = 3 to start and stop the drive with the master
device using serial communications. Set b1-01 = 3
[Frequency Reference Selection 1 = Option PCB] to use
Description
YASKAWA TOEP C730600 83A CC-Link Installation Manual
Default
(Range)
1
(0 - 4)
1
(0 - 3)