Figure 44. W_HE casing 4 & 5 supply fan performance curve
8.0
7.5
7.0
1200 RPM
6.5
6.0
1100 RPM
5.5
5.0
1000 RPM
4.5
4.0
900 RPM
3.5
3.0
800 RPM
2.5
700 RPM
2.0
600 RPM
1.5
500 RPM
1.0
0.5
0.0
0
2000
4000
6000
Figure 45. W_HE casing 6 supply fan performance curve
8.0
1200 RPM
7.5
1100 RPM
7.0
1000 RPM
6.5
6.0
5.5
900 RPM
5.0
4.5
800 RPM
4.0
3.5
700 RPM
3.0
10 HP
2.5
600 RPM
7.5 HP
2.0
500 RPM
1.5
1.0
0.5
0.0
0
3000
6000
RT-SVX35H-EN
30 HP
25 HP
20 HP
15 HP
10 HP
7.5 HP
5 HP
8000
10000
12000
14000
16000
CFM
50 HP
40 HP
30 HP
25 HP
20 HP
15 HP
9000
12000
15000
18000
CFM
40 HP
18000
20000
22000
24000
26000
21000
24000
27000
30000
System Start-up
W_HE Casing 4 & 5
Dual 20 X 20 Fans
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 7.5
- Maximum Motor HP
C40, C50 = 30 HP
40% WOCFM
- Maximum Fan RPM
7.5 - 15 HP = 1141
20 - 30 HP = 1170
- Maximum CFM
4 = 18,000
5 = 22,500
50%
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
60%
70%
80%
90%
28000
30000
W_HE Casing 6
Dual 22 X 22 Fans
40% WOCFM
Entrance Losses
- without Evap Coil
- without Filters
- without Return Air Dampers
- without Exhaust
Fan Curve Limits
- Minimum Motor HP = 10
- Maximum Motor HP = 50
- Maximum Fan RPM = 1130
- Maximum CFM = 27,000
50%
- Maximum Static Pressure
Leaving the Unit = 4.0" w.c.
60%
70%
80%
90%
33000
36000