Gas Heating Sequence Of Operation - Trane IntelliPak WEHE Series Installation, Operation And Maintenance Manual

Commercial rooftop air handlers with cv, vav, or szvav controls
Table of Contents

Advertisement

closing "Stage 1" (K10 on SCM or K11 on MCM). After the
first functional stage has started, the compressor module
monitors the saturated refrigerant temperature and closes
the condenser fan output contact "1A", when the saturated
refrigerant temperature rises above the "lower limit"
setpoint.
Units with Traq™Sensor
The fresh air enters the unit through the Traq™ Sensor
assembly and is measured by velocity pressure flow rings.
The velocity pressure flow rings are connected to a
pressure transducer/solenoid assembly. The solenoid is
used for calibration purposes to compensate for
temperature swings that could affect the transducer. The
Ventilation Control Module (VCM) utilizes the velocity
pressure input, the RTM outdoor air temperature input,
and the minimum outside air cfm setpoint to modify the
volume (cfm) of fresh air entering the unit as the measured
airflow deviates from setpoint.
When the optional temperature sensor is installed and the
Preheat function is enabled, the sensor will monitor the
combined (averaged) fresh air and return air
temperatures. As this mixed air temperature falls below
the Preheat Actuate Temperature Setpoint, the VCM will
activate the preheat binary output used to control a field
installed heater. The output will be deactivated when the
temperature rises 5° above the Preheat Actuate
Temperature Setpoint.
When the optional CO
sensor is installed and the CO
2
Reset is enabled, as the CO
above the CO
Reset Start Value, the VCM will modify the
2
minimum outside air cfm setpoint to increase the amount
of fresh air entering the unit. The setpoint will be adjusted
upward until the CO
Maximum Reset Value is reached.
2
The maximum effective (reset) setpoint value for fresh air
entering the unit is limited to the systems operating cfm.
As the CO
concentration decreases, the effective (reset)
2
setpoint value is adjusted downward toward the minimum
outside air cfm setpoint.
Figure 37. C0
reset
2
RT-SVX35H-EN
concentration increases
2
Units equipped with 100% modulating
exhaust
The exhaust dampers are controlled through an Exhaust/
Comparative Enthalpy Module (ECEM). The ECEM
receives input form a space transducer and modulates the
exhaust dampers to maintain the space pressure to within
the specified setpoint controlband.

Gas Heating Sequence of Operation

Standard Two Stage Gas Furnace
The control systems for the rooftop units are wired to
ensure that the heating and cooling cannot occur
simultaneously. A typical electrical schematic for the
Fenwal and Honeywell ignition control system is
illustrated in
Figure 38, p. 68
the wiring diagram while reviewing the following
sequence of operation.
Honeywell Ignition System
When a heating requirement exists, the Rooftop Module
(RTM) starts the supply fan and sends a request for heat to
the Heat Module. The Heat Module closes K1 contacts and
starts the combustion blower motor (4B11). The
combustion blower motor starts on low speed through the
normally closed combustion blower relay (4K33) contacts.
The supply airflow switch (4S38) and the combustion air
switch (4S25) closes. Power is applied through the high
2
limit cutout (4S26) to the Honeywell ignition control board
(4U18). The ignition control board (4U18) starts a prepurge
timing cycle. At the end of the prepurge cycle, the ignition
transformer (4T7) and the pilot solenoid valve (4L9) are
energized. This starts a 10 second trial for pilot ignition.
When the pilot flame is established and sensed by the
flame sensing rod (4U19), stage 1 of the main gas valve
(4L7) and the 60 seconds sequencing time delay relay
(4DL6) is energized.
The system will operate in the low heat mode until there
is an additional call for heat is established by closing the
K3 contacts on the Heat Module.
System Start-up
and
Figure 39, p.
69. Refer to
65

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents