Table 17. GBAS Voltage vs. Setpoint
Setpoint
Occ Zone Cooling Setpoint(CV only)
Unocc Zone Cooling Setpoint
Occ Zone Heating Setpoint(CV only)
Unocc Zone Heating Setpoint
SA Cooling Setpoint (VAV only)
SA Cooling Setpoint (SZVAV only)
Zone Cooling Setpoint (SZVAV only)
SA Heating Setpoint (VAV only)
SA Heating Setpoint (SZVAV only)
Space Static Pressure Setpoint
SA Static Pressure Setpoint
Min OA Flow Setpoint 1
MWU Setpoint
Econ Dry Bulb Enable Setpoint
SA_Reheat_Setpoint
Minimum Position Setpoint 3
Occ Dehumidification Setpoint
Unocc Dehumidification Setpoint
Occ Humidification Setpoint
Unocc Humidification Setpoint
Notes:
1. If DCV is enabled this is used for Design Minimum OA Flow Setpoint
2. If DCV is enabled, this is used for Design Minimum OA Damper Position Setpoint
Table 18. GBAS 0-10 VDC output range
Setpoint
Outdoor Air Temperature
Zone Temperature
Supply Air Temperature (VAV only)
Supply Air Pressure (VAV only)
Space Pressure
Space RH
OA RH
Space CO2 Level
Cooling Capacity%
Heating Capacity%
Outdoor Air Damper Position
Outdoor Airflow
RT-SVX35H-EN
GBAS 0-5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
0.5 to 4.5 VDC
GBAS 0-10vdc
Valid Range
0.5 to 9.5vdc
-40 to 200°F
0.5 to 9.5vdc
-40 to 200°F
0.5 to 9.5vdc
-40 to 200°F
0.5 to 9.5vdc
0.0 to 7.91 wc
0.5 to 9.5vdc
-0.67-0.67 wc
0.5 to 9.5vdc
0.5 to 9.5vdc
0.5 to 9.5vdc
50-2000 PPM
0.5 to 9.5vdc
0.5 to 9.5vdc
0.5 to 9.5vdc
0.5 to 9.5vdc
0 to 65,000 CFM
GBAS 0-10 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
-0.20 to 0.30 IWC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0 to Unit Max Flow
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0.5 to 9.5 VDC
0-100%
0-100%
0-100%
0-100%
0-100%
Installation
Valid Range
50 to 90°F
50 to 90°F
50 to 90°F
50 to 90°F
40 to 90°F
40 to 70°F
50 to 80°F
40 to 180°F
65 to 95°F
0.7 to 5.1 IWC
50 to 90°F
50 to 140°F
60 to 90°F
0 to 100%
40 to 65%
40 to 65%
20 to 50%
20 to 50%