Sequence of Operation

Terminology

Controls
RRUCM
RRU Main Control Module
ROD
Remote Operator Display
DES
Outdoor Damper End Switch
APS
Air Proving Switch
FFS
Fan Failure Switch
RCC
Refrigeration Capacity Controller
MGA
Modulating Gas Actuator
GV
Gas Valve
IGN
Ignition Control Module
TNS5
Gas Ignitor
TNS6
Gas Ignitor Power Transformer
HTC
High Temperature Cutout
RTRM
ReliaTel Refrigeration Module
RHV
Reheat Valve
SSP
Space Temperature Set Point (Dial)
ODA
Outdoor Air Damper Actuator
RDA
Return Air Damper Actuator
R
24VAC Power - Terminal R (RTRM)
G
Indoor Fan Motor – Terminal G (RTRM)
Y1
Cooling Stage 1 – Terminal Y1 (RTRM)
Y2
Cooling Stage 2 – Terminal Y2 (RTRM)
LTB
Low Voltage Terminal Block
RRUTS
Control Terminal Strip (Field Connections)
Relays
R1
ODR / RDR (O/Air & R/Air Damper Actuator)
R2
IDM (Indoor Fan Motor)
R3
COOL 1 (Cooling – Stage 1)
R4
COOL 2 (Cooling – Stage 2)
R5
HGRH (Hot Gas Reheat Valve)
R6
HEAT (Heat Relay)
R7
PV (Gas Valve & Gas Ignitor)
R8
MV (Gas Ignitor Disconnect)
R9
ESR (Emergency Stop Relay)
Sensors
OTS
Outdoor Air Temperature (OAT)
STS
Supply Air Temperature (SAT)
STC
Space Temperature (ST)
ORH
Outdoor Humidity (ORH)
SHC
Space Humidity (SRH)
Operator Set Points
CSP
Y1 – O/Air Cooling Enable
OES1
Y1 – O/Air Dehumid Enable
OES2
Y2 – O/Air Dehumid Enable
HESP
O/Air Heating Enable
HSP
Occupied S/Air Heating
MHSP
Minimum Supply Air Heating
SLC
S/Air Low Cutoff (Time)
SLT
S/Air Low Cutoff (Temperature)
SHC
S/Air High Cutoff (Time)
SHT
S/Air High Cutoff (Temperature)
Optional—Requires Hot Gas Reheat
(HGRH)
HGRHD
HGRH Control Dead Band
RRU-SVX01F-EN
Optional—Requires Space Temperature &
RH Sensors
OSSP
Occupied Space Cooling
OSHO
Occupied Space Heating Offset
OSRS
Occupied Space Humidity
NHSP
Unoccupied Space Heating
NCSP
Unoccupied Space Cooling
NRSP
Unoccupied Space Humidity
NSAS
Unoccupied S/Air Heating
Power On—Control Input
"Occupied"
Three Phase Unit Disconnect ON
RRUCM and RTRM Initialize
Control Input Contact CLOSED at RRUTS – 7 & 8
"Occupied" Ventilation Mode
RRUCM Energizes the O/Air Damper Actuator (ODA)
through ODR / RDR Relay R1
O/Air Damper OPENS
R/Air Damper (Optional) CLOSES through ODR / RDR
Relay R1
O/Air Damper makes the Outdoor Damper End Switch
(DES)
RRUCM Energizes the Indoor Fan Motor (IDM) through
IDM Relay R2
R2 Energizes RTRM Terminal G and IDM STARTS
Fan Failure Switch (FFS) Proves Airflow
VENTILATION MODE Established
"Occupied" Conditioning Modes
Outdoor Air Temperature (OTS) and Outdoor Air Relative
Humidity (ORH) sensors located in the Outdoor Air Inlet
controls call for the following operational modes based on
Outdoor Air conditions.
COOLING MODE
Compressor 1 ON
DEHUMIDIFICATION MODE
Compressor 1 or Compressor 1 & 2 ON
HOT GAS REHEAT (OPTIONAL)
Compressor 1 or Compressor 1 & 2 ON
HEATING MODE
Modulating Heat
"Occupied" Cooling Mode
Call for cooling is based on Outdoor Air Temperature
(OAT) sensed at the Outdoor Air Temperature Sensor
(OTS). Y1 – O/Air Cooling Enable Set Point (CSP) is
operator adjustable between 68 F and 80°F.
19