8.8 Airflow Direction Control
TOP PREVIOUS NEXT
When set a Airflow Direction Auto-Control with remote control, the louver swings up and
●
down as shown in the diagram.
The louver does not swing when the Indoor Fan Motor stops during operation at the upper
●
limit.
When stopped with remote control, the discharge vent is reset, and stopped at the closing
●
position.
During Anti-dew condensation prevention, Airflow Direction Auto-control angle change from
●
0° - 36° to 12° - 28° under Cooling and Soft Dry operation mode.
1. There is no swinging while indoor fan motor is stopped during Cooling and Soft Dry operation.
2. When the intake air temperature reaches 38°C, the louver is changed from upper to lower limit. When the intake air temperature falls
to 35°C, the louver is changed from louver to upper limit.
When the manual Airflow Direction Selection Button is pressed, the automatic airflow is
●
released and the airflow direction louver move up and down in the range shown in the diagram.
The louver can be adjusted by pressing the button to the desired louver position.
When the remote control is used to stop the operation, the discharge vent is reset, and stopped
●
at the closing position.
During Anti-dew condensation prevention, Airflow Direction Manual control angle change
●
from 14°, 19°, 24°, 30°, 36° to 16°, 18°, 20°, 22°, 24° under Coolingand Soft Dry operation
Vertical Airflow Direction Auto-Control
Vertical Airflow Direction manual Control