8.3 Heating Mode Operation
TOP PREVIOUS NEXT
Heating in operation according to Remote Control setting.
●
When the compressor is stopped by Power Switch, Remote Control or there is a power failure,
●
it restarts after 3 minutes when the Power Switch, Remote Control is turned ON or the power
supply is resumed.
When the setting temperature is reached during heating operation, the compressor stops and it
●
will not start for 4 minutes.
(a) Outdoor Fan Control
If the temperature of the Outdoor Heat Exchanger less than -3°C, Outdoor Fan is ON. The
●
Outdoor Fan stop, when Outdoor Heat Exchanger temperature is Tb or more according to
Outdoor Air Temperature region as table below:
The Outdoor Fan restarts when the indoor heat exchanger temperature falls to 49°C.
During starting of Heating mode and after deice, Outdoor Fan ON for 90 sec. (Hi).
(b) Compressor High Pressure Control
If the indoor heat exchanger becomes 68°C or more, the compressor will stop and restart
●
automatically.
(Time Delay Safety Control - 4 minutes waiting).
Time Delay Safety Control
Overload Protection Control