User Manual
GFK-2883F
in the grounded mounting panel or enclosure, using a machine screw, star lock washer and
flat washer. Alternately, if the panel has a ground stud, use a nut and star lock washer for
each wire on the ground stud to ensure adequate grounding. Where connections are made
to a painted panel, the paint should be removed so clean, bare metal is exposed at the
connection point. Terminals and hardware used should be rated to work with the aluminum
Carrier material.
Note:
Figure 11: Grounding Diagram
3.2

Installing Modules on the Carriers

The insertion and removal of I/O modules is the same as in a RX3i Universal Backplane. For
details, refer to, the PACSystems RX3i System Manual, GFK-2314.
CAUTION
Do not install a Power Supply module on the CEP or CEE Carrier. Attempting to do so could
damage the module and/or the Carrier
3.2.1

Unsupported Modules

CAUTION
If an unsupported module is inserted in the CEP or CEE Carrier, the module will not be
recognized correctly and could cause damage to the Carrier or the module.
When an unsupported I/O module is inserted in either the RX3i CEP Carrier or RX3i CEE
Expansion Carrier, no alarm is reported to indicate this.
Some unsupported I/O modules have the same Distinguishing Class (for example,
IC694MDL740 has the same Distinguishing Class as IC694MDL742). Refer to Section 1.6,
Supported I/O Modules.
Installation & Mounting
The star lock washer method is suitable for a shield ground, but not suitable for a safety
ground.