If a discrete output or discrete mixed module does not have a switch or an additional
configuration option specifying its output's default action, the hardware default is to Force
outputs off.
Configuring Analog Modules that have Jumpers
Some PACSystems RX3i analog modules have jumpers on their terminal strips that control
the operation of their I/O. For example, the IC69xALG220 can operate as a +10vdc to -10vdc
analog input or a 4-20mA analog input depending on a jumper setting. Similarly, the
IC69xALG390 uses a jumper rather than a DIP switch to control Force Off or Hold Last State
operation.
Jumper settings are latched when the module is started, so the jumper setting cannot be
altered during operation. The RX3i CEP Carrier must be power-cycled for the new jumper
setting to be re-evaluated or the module must be removed, then hot-inserted.
4.2.3

Configuring Module Parameters

After adding PACSystems RX3i modules to the remote IO-Device, their parameters must be
configured. For all PACSystems RX3i modules, this includes configuring a set of basic
parameters such as reference address. Configuration details for those basic parameters are
given on the following pages. If the module has no module-specific parameters, a blank
grouping of Module Parameters may be displayed in the Configuration Tool.
The RX3i modules listed in the following table require additional configuration beyond the
basic parameters described in this chapter. Refer to the PACSystems RX3i System Manual,
GFK-2314; or the individual module datasheet for detailed parameter information.
Catalog Number
IC693ALG222
IC693ALG223
IC693ALG392
IC693ALG442
IC694ALG222
IC694ALG223
IC694ALG392
IC694ALG442
IC694PSM001
IC695ALG112
IC695ALG312
IC695ALG600
IC695ALG616
Configuration
Module Description
Analog Voltage Input Module – 16 Channel
Analog Current Input Module – 16 Channel
Analog Current/Voltage Output Module – 8 Channel GFK-2557
Analog Module, 4 Inputs / 2 Outputs
Current/Voltage
Analog Voltage Input Module – 16 Channel
Analog Current Input Module – 16 Channel
Analog Current/Voltage Output Module – 8 Channel GFK-2557
Analog Module, 4 Inputs / 2 Outputs
Current/Voltage
Power Sync and Measurement Module
Isolated Analog Current/Voltage Input Module – 12
Channel
Isolated Thermocouple Input Module, 12 Channels
Universal Analog Input Module – 8 Channel
Analog Current/Voltage Input Module – 16 Channel
Chapter 4
Sep 2019
Datasheet
GFK-2654
GFK-2655
GFK-2687
GFK-2654
GFK-2655
GFK-2687
GFK-2748
GFK-2482
GFK-2500
GFK-2348
GFK-2372
32